Installing the Elevator Restriction Unit
Elevator Restriction System Installation and Operation Manual
33
2.10.2
Maximum Power Supply Wire Distances
The distance from the ERU to the power supply is a function of the wire gauge
and the resistance generated by the cable by the power draw.
Do not exceed the maximum distances from the ERU to the power supply as
Table 2:
Maximum Power Supply Wire Distances
2.11
Firmware Update
You can update the firmware on your panel with the TX3 Configurator software
by using one of the following methods.
•
Firmware Upgrade Wizard
•
Network Firmware Upgrade
The Firmware Upgrade Wizard can be used to update only one panel at a time. It
will work on any panel.
The Network Firmware Upgrade procedure can update more than one panel at
the same time. In order to use the Network Firmware Upgrade, all of the panels
must already have firmware that supports this feature installed on them.
Refer to LT-995 TX3 System Configuration and Administration Manual for
instructions on how to perform both of these firmware upgrade methods. LT-995
can be found on the TX3 Configurator Software installation CD, USB flash
drive, or on the Mircom website.
2.12
System Configuration
See LT-995 TX3 System Configuration and Administration Manual for
instructions on configuring an elevator restriction system.
Gauge
Distance
16
125 ft (38.1 m)
14
200 ft (60.96 m)
12
320 ft (97.536 m)
10
500 ft (152.4 m)