2.3.1
2012E Relay Board
Each relay board has 12 Form C relay contacts rated at 0.25 A max. / 100 VDC
max.
Figure 9.
2012E Elevator Restriction Relay Board
2.3.1.1
2012E Relay Board Components
JW1-12
. Jumpers for selecting normally open or normally closed relay
operation. By default the relays are normally open.
For example, if you want relay 1 to be normally closed, then put the jumper on the
top two pins of JW1. If you want relay 1 to be normally open, then put the jumper
on the bottom two pins of JW1.
I1-12
. LEDs indicating when each relay is active.
Relays 1 to 12
. Screw terminal contacts for each relay.
R E L A Y 5
R E L A Y 6
R E L A Y 7
R E L A Y 8
R E L A Y 9
R E L A Y 1 0
R E L A Y 1 1
R E L A Y 1
R E L A Y 2
R E L A Y 3
R E L A Y 4
R E L A Y 1 2
C o m
N O / N C
C o m
N O / N C
C o m
N O / N C
C o m
N O / N C
C o m
N O / N C
C o m
N O / N C
C o m
N O / N C
C o m
N O / N C
C o m
N O / N C
C o m
N O / N C
C o m
N O / N C
C o m
N O / N C
NC
NO
NC
NO
NC
NO
NC
NO
NC
NO
NC
NO
NC
NO
NC
NO
NC
NO
NC
NO
NC
NO
NC
NO
JW1
JW2
JW3
JW4
JW5
JW6
JW7
JW8
JW9
JW10
JW11
JW12