QMT-5300A, QMT-5302 and QZT-5302 Installation and Operation Instructions

3

QZT-5302 Zone Adder Wiring

Fig

ure 

2 shows the wiring for QZT-5302. The P1 Cable plugs into P1 on the QMT-5300A or QMT-5302 Master 

Telephone for the first Zone Adder, or into P2 of the previous Zone Adder for additional Zone Adders. The Jumper 
plug is removed from JW1 on each QZT-5302 and placed on the last QZT-5302.

The Telephone Zones connect to telephone circuits marked Out and Ret (return)  terminals, numbered from 1 to 12. 
The 10 K ohm ELR resistors that are shipped with the panel are moved to the last Remote Telephone on each Zone 
(for Class B) and the negative to negative black wire jumper is removed when using class B wiring.  

For Class A, each telephone zone is wired out from the OUT + - terminals to the remote telephones and back to 
terminals RET  + and -.   Also for Class A wiring both the red and black wire jumpers found on the positive and 
negative terminals of the QZT-5302 are removed.  

Note that on each QZT-5302, the associated buttons for Telephone Zones 1 to 12 are numbered left to right, where 
Zones 1 to 6 are the top row, and 7 to 12 are the bottom row.

Figure 2: QZT-5302 Zone Adder Wiring

TELEPHONE ZONE, WIRE TO  FT-300 OR OTHER COMPATIBLE

REMOTE TELEPHONES.  CONNECT 10K ELR RESISTOR AFTER

THE LAST REMOTE TELEPHONE FOR CLASS B AND REMOVE

THE BLACK JUMPER FROM OUT - and RET - TERMINALS .  FOR

CLASS A WIRING OF TELEPHONE ZONE, WIRE OUT + - AND BACK

FROM LAST TELEPHONE TO RET + -.

+

-

+

-

OUT 1

RET 1

+

-

RET 12

OUT 12

+

-

QZT-5302

RETURN FOR CLASS A WIRING

RETURN FOR CLASS A WIRING

NOTE:

 REMOVE WIRE JUMPERS BETWEEN POSTIVES

AND NEGATIVES WHEN WIRING ZONES AS CLASS A.

FOR CLASS B ONLY THE WIRE JUMPER BETWEEN

NEGATIVES IS REMOVED.

TELEPHONE ZONE, WIRE TO  FT-300 OR OTHER COMPATIBLE

REMOTE TELEPHONES.  CONNECT 10K ELR RESISTOR AFTER

THE LAST REMOTE TELEPHONE FOR CLASS B AND REMOVE

THE BLACK JUMPER FROM OUT - and RET - TERMINALS .  FOR

CLASS A WIRING OF TELEPHONE ZONE, WIRE OUT + - AND BACK

FROM LAST TELEPHONE TO RET + -.

Summary of Contents for QMT-5300A

Page 1: ...302 and QZT 5302 Firefighters Telephone System LT 674 Rev 2 Dec 2007 Installation Operation Instructions Advanced Life Safety Solutions COMMON TEL TROUBLE LAMP TEST INCOMING CALL MASTER TEL TROUBLE CO...

Page 2: ......

Page 3: ...Multi Zone Slide in label NP 896 is provided with the QMT 5302 use the Connect for Single Zone or Clear All label for Multi Zone The QZT 5302 includes blank labels for Telephone Zone information Chas...

Page 4: ...ter Telephone is being used as a Multi Zoned System with QZT 5302s the NP 736 Label is used or Clear All label from NP 896 and a Jumper is placed on JW3 only The TEL CKT terminals are left as is Telep...

Page 5: ...ire jumpers found on the positive and negative terminals of the QZT 5302 are removed Note that on each QZT 5302 the associated buttons for Telephone Zones 1 to 12 are numbered left to right where Zone...

Page 6: ...back On Hook 3 Press the CLEAR ALL button to disconnect all Zones 4 Press LAMP TEST to test all indicators Indicators on QMT 5300A or QMT 5302 Common Tel Trouble This LED will flash amber if there is...

Page 7: ...erates only by AC power any interruption however brief will render that device inoperative while it does not have power Power interruptions of any length are often accompanied by voltage fluctuations...

Page 8: ...other noise sources such as stereos radios televisions air conditioners or other appliances or passing traffic Audible notification appliances however loud may not be heard by a hearing impaired pers...

Page 9: ...ed by failure to provide a suitable installation environment for the products damage caused by use of the products for purposes other than those for which it was designed damage from improper maintena...

Page 10: ...product will be charged for each replacement unit WARNING Mircom Technologies Ltd recommends that the entire system be completely tested on a regular basis However despite frequent testing and due to...

Page 11: ......

Page 12: ...Tel 905 660 4655 Fax 905 660 4113 Mircom 2007 Printed in Canada Subject to change without prior notice www mircom com Advanced Life Safety Solutions U S A 60 Industrial Parkway PMB 278 Cheektowaga NY...

Reviews: