QMT-5300A, QMT-5302 and QZT-5302 Installation and Operation Instructions

1

QMT-5300A, QMT-5302 and QZT-5302 Instructions

Introduction

MIRCOM’s Fire Fighters’ Telephone may be used either alone as a Single Zone System (using the QMT-5300A or 
QMT-5302 Master Telephone by itself), or as a Multi-Zoned System (with the QZT-5302 Zone Adders).

Mounting

The modules mount in any of the BB-1000 Series Remote Annunciator enclosures except for the QMT-5302 Master 
Telephone which mounts into a BB-5008 or BB-5014 backbox. For the QMT-5300A Master Telephone, the included 
extended window module must be installed in place of the existing window. In any BB-1000 enclosure, the QMT-
5300A is mounted bottom-most, and one to five QZT-5302s above, for a total of 60 Telephone Zones.  In any BB-
5008 enclosure, the QMT-5302 should be mounted below the QZT-5302s and beside the master telephone for ease 
of ribbon cable installation.

Labels

Two slide-in labels are supplied with the QMT-5300A ; the NP-735 is used for Single Zone and the NP-736 for Multi-
Zone. Slide-in label NP-896 is provided with the QMT-5302, use the Connect for Single Zone or Clear All label for 
Multi-Zone.   The QZT-5302 includes blank labels for Telephone Zone information.

Chassis Ground

Connect one of the BB-1000 Series Backbox, BB-5008 or BB-5014 Earth-Ground points (Chassis Ground) to Earth 
Ground (cold water pipe).

Power Supply

Only the telephone master QMT-5300A or QMT-5302 module requires power. It can be powered with a 24 VDC, 
200 mA external DC power source (filtered or un-filtered, such as 4-wire smoke or auxiliary power from a Fire Alarm 
Control Panel), see Fig.1

Jumpers

There are three jumpers on the QMT-5300A and QMT-5302 PCB showing at the top of the black chassis. For a 
Single-Zoned System  JW1 and JW2 have jumpers installed, JW3 does not. For a Multi-Zoned system with QZT-
5302s, JW1 & JW2 jumpers are removed, and JW3 is installed. There is one jumper, JW1, on each QZT-5302 Zone 
Adder, and a jumper is installed only on the last QZT-5302.

Connectors

On the QMT-5300A and QMT-5302, P1 is used only for Multi-Zoned Systems.  P2 is the connection for the Master 
Telephone Handset.  On the QZT-5302, P1 connects to the QMT-5300A, QMT-5302 or previous QZT-5302, and P2 
connects to the next QZT-5302.

Summary of Contents for QMT-5300A

Page 1: ...302 and QZT 5302 Firefighters Telephone System LT 674 Rev 2 Dec 2007 Installation Operation Instructions Advanced Life Safety Solutions COMMON TEL TROUBLE LAMP TEST INCOMING CALL MASTER TEL TROUBLE CO...

Page 2: ......

Page 3: ...Multi Zone Slide in label NP 896 is provided with the QMT 5302 use the Connect for Single Zone or Clear All label for Multi Zone The QZT 5302 includes blank labels for Telephone Zone information Chas...

Page 4: ...ter Telephone is being used as a Multi Zoned System with QZT 5302s the NP 736 Label is used or Clear All label from NP 896 and a Jumper is placed on JW3 only The TEL CKT terminals are left as is Telep...

Page 5: ...ire jumpers found on the positive and negative terminals of the QZT 5302 are removed Note that on each QZT 5302 the associated buttons for Telephone Zones 1 to 12 are numbered left to right where Zone...

Page 6: ...back On Hook 3 Press the CLEAR ALL button to disconnect all Zones 4 Press LAMP TEST to test all indicators Indicators on QMT 5300A or QMT 5302 Common Tel Trouble This LED will flash amber if there is...

Page 7: ...erates only by AC power any interruption however brief will render that device inoperative while it does not have power Power interruptions of any length are often accompanied by voltage fluctuations...

Page 8: ...other noise sources such as stereos radios televisions air conditioners or other appliances or passing traffic Audible notification appliances however loud may not be heard by a hearing impaired pers...

Page 9: ...ed by failure to provide a suitable installation environment for the products damage caused by use of the products for purposes other than those for which it was designed damage from improper maintena...

Page 10: ...product will be charged for each replacement unit WARNING Mircom Technologies Ltd recommends that the entire system be completely tested on a regular basis However despite frequent testing and due to...

Page 11: ......

Page 12: ...Tel 905 660 4655 Fax 905 660 4113 Mircom 2007 Printed in Canada Subject to change without prior notice www mircom com Advanced Life Safety Solutions U S A 60 Industrial Parkway PMB 278 Cheektowaga NY...

Reviews: