background image

 

 

LT-6041 Rev 3 

 

 

Terminal 

Function 

AM  

Return for AP signal. Connects to QMP-510X terminal PTT IN - 

QP 

Connects to push to talk input on QIF-5000 (J2 terminal 1). This 
input is used to activate paging function of the QX-5000 system. 

QM 

Return for QP signal. Connect to QIF-5000 J2 terminal 2. 

Across PC terminals 

Paging active dry contact. Closes when external signals or QX-5000 
paging is active.  

QA 

Connect to QIF-5000 paging signal input. (J1 terminal 1) 

QR 

Return for QA. Connects to QIF-5000 J1 terminal 2. 

AA 

Connection for audio line from QMP-510X series remote paging 
microphone consoles. Connects to QMP-510X MIC IN + terminal. 

AR 

Return for AA. Connects to QMP-510X MIC IN - terminal. 

AS (two terminals) 

Connection for shield of cables connected to QA,QR and AA,AR 

VI 

24VDC input. Connect to QIF-5000 J2 terminal 8. 

0 (two terminals) 

0V power return for VI and VO. Connect one to QIF-5000 J2 
terminal 7 and the other to the QMP-501X 24VDC IN – terminal. 

VO 

24 VDC output. Connect to first QMP-510X series remote paging 
console. Connect to QMP-501X 24VDC IN + terminal. 

 

Jumpers identification table 

 

Jumper 

Function (when inserted) 

Z1 (two jumpers) 
 

Signal 1 audio line supervision enable. Both jumpers must be 
installed and a 3.9K end of line resistor is required. In addition, 
coupling capacitors may be needed on signal output to prevent 
disruption of supervision voltage. 

Z2 to Z4 

Same function as Z1 but used for signal lines 2 to 4. 

O1 

Open detection for Zone 1 signal line. Must be removed when Z1 
jumpers are not installed. 

O2 to O4  

Same function as O1 but used for signal lines 2 to 4. 

X1  

Control input #1 supervision and polarity. See figure XXX for 
possible combinations. 

X2 to X4  

Same function as X1 but used for signal lines 2 to 4. 

SE 

Enables short circuit detection on signal lines input. 

Ground fault detection enable on external signal side. Detection is 
performed by the QIF-5000.  

A. PRIO 1 to 4 

Disable external signals 1 to 4 during alarm condition on QX-5000. 

P. PRIO 1 to 4 

Disable external signals 1 to 4 during QX-5000 paging activation. 

 

Summary of Contents for QIF-2011

Page 1: ...h the audio and the control inputs wiring can be supervised for faults by setting the appropriate jumper When supervision is required 3 9K Ohms end of line resistors must be connected to each control...

Page 2: ...onged to zone 3 instead of zone2 Terminal identification table Terminal Function SH beside R1 Audio signal shield connection R1 External signal 1 audio return H1 External signal 1 audio positive Conne...

Page 3: ...signal 4 70VRMS maximum M4 External signal 4 control input return C4 External signal 4 control input positive M4 and C4 typically connect to normally open dry contact used to activate input 4 A1 Comma...

Page 4: ...501X 24VDC IN terminal VO 24 VDC output Connect to first QMP 510X series remote paging console Connect to QMP 501X 24VDC IN terminal Jumpers identification table Jumper Function when inserted Z1 two...

Page 5: ...S CONFIGURATION WITH BOARD VIEWED AS IN FIGURE 1 LEDs and potentiometers identification tables LEDs POTs Function OK Green led indicating that interface is operational CS Yellow LED indicating short c...

Page 6: ...t then the emergency paging source and finally the background music source Both paging sources have priority over the alarm signals but the background music must be interrupted for the duration of an...

Page 7: ...ound music A 3 9K End of line resistor must be installed at the fire alarm panel to provide supervision for the command line for the external emergency paging signal Configuration In the QX 5000 confi...

Page 8: ...following diagrams provide wiring information for the QIF 2011 for the typical configuration described above Figure 3 QIF 2011 connection on signal side for the typical system described Please see tex...

Page 9: ...connections for typical system described above See text and figure 7 for other configurations Note Only connections used for the QIF 2011 are shown For other connections on the QIF 5000B J3 to J5 ter...

Page 10: ...5000B wiring for signal lines for any signal configurations Note only connections used for the QIF 2011 are shown For other connections on the QIF 5000B J1 and J2 terminal blocks please consult QX 500...

Page 11: ...QMP 510X connections for any signal configuration Note only connections used for the QIF 2011 are shown For other connections on the QMP 510x terminal blocks and connectors please consult QX 5000 man...

Page 12: ...ion If only all call is required for all external signals connection to a QIF 2000 is not necessary and the QIF 2011 can be connected to opto input 3 or 4 on the QIF 5000B if those are free The config...

Page 13: ...ntroller The signal side connections remain the same but the connections to the ANC 5000 must be done as per figure 8 Priority jumpers must be removed and jumper JW27 on the QIF 2011 must be set as sh...

Page 14: ...nputs open circuit detection voltage Rx to Hx 4 1V 10 Signal inputs short circuit detection voltage Rx to Hx 0 75 V 10 Control inputs short circuit detection voltage Rx to Hx 0 75 V 10 QMP 501X PTT in...

Page 15: ...m external source voltage for full power audio output on QX 5000 Potentiometer adjusted for maximum gain 250mV RMS Maximum voltage at external low voltage signal inputs 1 to 4 2VRMS Minimum external s...

Reviews: