41
5.11.2
Setting the Password
By default, no password is required to press the control buttons and enter the operation menu.
Sets the password for all three access levels. The minimum number of digits for a password is
4. For changing a specific level of password the password required is the equivalent level or
higher level.
The user is prompted to enter the access level for which the password needs to be changed.
The user is then prompted to enter the current access level or higher level password. The
maximum number of digits allowed is ten (10).
If an incorrect password is entered an invalid password message displays on the shared LCD.
The user is given three attempts to enter the correct password. After three failed attempts the
display reverts back to the main operation menu.
If the password is correct the user is prompted to enter the new password and press the
Enter
button.
To confirm the password the user is prompted to re-enter the password and press the
Enter
button.
5.11.3 Reports
Overview
Reports can be generated in command mode from the reports menu. Reports can be
displayed in a special format on the shared display for the following items:
1. Alarm log
The alarm log report displays the contents of the alarm event log on the shared display which
contains the last 400 of any of the following events:
Access Level :1
Enter password
__________
Invalid password
Enter new password
__________
Re-enter password
__________
R e p o r t M e n u
1 . A l a r m L o g
2 . E v e n t L o g
3 . C u r r e n t L e v e l s
4 . V e r i f C o u n t s
5 . M a i n t R e p o r t
6 . M / P R e p o r t