Additional Operation Features
•
The panel can synchronize strobes directly without the use of the synchronous module.
•
Depending on the device, the system can detect open and short troubles and report it as
an output circuit trouble.
5.3.1
Signal Output
For audible devices such as bells and piezo mini-horns. Signals operate in alert (two stage)
and/or evacuation rate.
5.3.2
Strobe Type Settings
Normal (non-synchronized)
•
Strobe circuits operate similar to signals except that they are always turned ON
continuously (they are not affected by the alert or evacuation rates) if configured as
Normal.
•
Configuring strobes as Normal does not use a sync protocol for the output circuit.
•
Silenceable or non-silenceable.
Synchronized
Output circuits can be configured with various synchronization protocols.
When the output circuit is configured as strobe and also configured as non-silenceable and the
device used on the output is a combination of horn and strobe, then if the signal silence is
activated while the circuit is active the horn(s) are silenced while the strobe keeps on flashing.
Synchronized strobes and strobe/horn models of the following manufacturers are supported:
Mircom, System Sensor, Wheelock and Gentex.
5.3.3
Relay Output
Un-bypassed relay outputs are activated if any un-bypassed input circuit or common system
status which has been programmed to it is active. If the relay is configured as silenceable it is
inhibited when common auxiliary disconnect is active. Relays also turned off if they are
bypassed or if all inputs and system status correlated to the Relay Output are restored or
bypassed.
Table 10 Configurable Output Types
Output Type
As listed in
Configurator
Description
located in
Section number
Device Types
Dual Relay Module
Supervised Output
Module
Relay
Relay
5.3.3
X
X
Signal
Signal
5.3.1
X
X
Strobe
Strobe
5.3.2
X
X
Note:
Silencing of the horn depends on the feature provided by the manufacturer of the
horn/strobe combination. Some models of the horn/strobe combination may not
have this feature and will not work as described above.