FleX-Net
TM
Installation and Operation Manual
123
ULI / ULC I ntegrated Fire Alarm and Audio Panel Specifications
Overall
PS- 2040 Pow er Supply
• 0 to 49 degrees Celsius, 0 to 93 + or - 2% RH (non-condensing) operating range
• Power input: 120 VAC, 60Hz, 12A or 240 VAC, 50Hz, 6A (primary), Not Power-limited
• Power supply ratings: 8.5A (x2), 18.85-0-18.85V (secondary)
13A, 29V (secondary)
Model QPS-5000N & QBC-5000N Pow er Supply & Charger
• Primary input 120 VAC, 60Hz, or 240 VAC, 50HZ, 12Amp, Not Power-limited
• Charging for up to 65 AH of 24 VDC batteries
• Float Type Charger
Model FNC- 2000 Fire Netw ork Controller Module
• Current consumption:
standby:
190mA
alarm:
190mA
Model ANC- 5000 Audio Netw ork Controller Module
• Current consumption:
standby:
255mA
alarm:
265mA
Model TNC- 5000 Telephone Netw ork Controller Module
• Current consumption:
standby:
195mA
alarm:
215mA
Model FOM- 2000- UM Fiber Optics Module
• Current consumption:
standby:
15mA
alarm:
15mA
Model QAA- 5160- 70/ 25 Amplifier w ith one 70V or 25V, 60 Watt Zone
• 70.7Vrms or 25V constant voltage output
• One fully supervised Class "A" or "B" speaker Zone
• 60 watts per zone
• Freq. Response:
ULI bandwidth from 800 to 2800 Hz
, ULC bandwidth from 400 to 4000 Hz
• Harmonic distortion less than 2.5% at 1 KHz
• Current consumption:
standby:
55mA
alarm:
350mA, plus 65mA/Watt Speaker Power
Model QAA- 5230- 70/ 25 Amplifier w ith tw o 70V or 25V, 30 Watt Zones
• 70.7Vrms or 25V constant voltage output
• Two fully supervised Class "A" or "B" speaker zones
• 30 watts per zone
• Freq. Response:
ULI bandwidth from 800 to 2800 Hz
, ULC bandwidth from 400 to 4000 Hz
• Harmonic Distortion less than 2.5% at 1 KHz
• Current Consumption:
standby:
55mA
alarm:
350mA, plus 65mA/Watt Speaker Power
Note:
All circuits are power limited, unless specified otherwise.