-1-
1. INTRODUCTION
The
FA-1025U
is a supervised 5 zone 24VDC Fire Alarm Control Panel.
The panel provides the following features:
- 5 class B detection zones
- 2 class B signal zones, 1.25A per zone
- Alarm and trouble relay contacts
- Remote trouble indication
- Remote supervised alarm annunciation
- Individual zone silence/disconnect switches
- Trouble silence switch
- Subsequent alarm operation
- LED indicators for zone Alarm and Trouble, A.C. On, Battery Fault, Ground Fault,
Remote Lamp Fail, Common Trouble, Signal Trouble and Signal Silenced
2. MECHANICAL INSTALLATION
The panel can be surface or flush mounted. Refer to Figure 1 for dimensions.
For surface mounting, mark the location of the four mounting holes. Install the top two screws into
the wall and place the panel over the screws. Install the bottom screws, and tighten down all four
screws.
For flush mounting, make the wall cut-out according to the panel dimensions. Remove the control
panel door. Mount the flush mounting trim (MODEL FA-102TRU) to the back box using the screws
and nuts provided with the flush mounting kit. Re-install the door on top of the flush trim. The cam
lock may require a minor adjustment in order to compensate for the flush trim.
3. FUNCTION SELECTION
The following jumpers are available for function selection, refer to Figure 2 for location;
JW1
Cut for normally open trouble contacts.
JW2
Cut for normally closed trouble contacts.
JW3
Cut to enable
common alarm
relay to de-energize if
signal silence
switch is activated.
JW6
Cut if
60 second signal silence
inhibit is not required (Signals can be manually
silenced any time if cut).
JW7
Cut to enable lamp supervision for the remote annunciator alarm zones.
Summary of Contents for FA-1025U
Page 2: ......
Page 4: ......
Page 9: ...5 FIGURE 1 BACKBOX FLUSH TRIM MOUNTING DETAILS...
Page 10: ...6 FIGURE 2 CIRCUIT BOARD LAYOUT...
Page 11: ...7 FIGURE 3 DETECTION AND SIGNAL WIRING INSTRUCTION...
Page 12: ...8 FIGURE 4 WIRING TABLE FOR DETECTION ZONE...
Page 13: ...9 FIGURE 5 WIRING TABLE FOR BELLS AND HORNS...
Page 14: ...10 FIGURE 6 ALARM TROUBLE RELAY CONTACTS AND REMOTE ANNUNCIATION WIRING INSTRUCTION...
Page 20: ......