1. INTRODUCTION

The

FA-1025U

is a supervised 5 zone 24VDC Fire Alarm Control Panel.

The panel provides the following features:

- 5 class B detection zones
- 2 class B signal zones, 1.25A per zone
- Alarm and trouble relay contacts
- Remote trouble indication
- Remote supervised alarm annunciation
- Individual zone silence/disconnect switches
- Trouble silence switch
- Subsequent alarm operation
- LED indicators for zone Alarm and Trouble, A.C. On, Battery Fault, Ground Fault,
 Remote Lamp Fail, Common Trouble, Signal Trouble and Signal Silenced

2. MECHANICAL INSTALLATION

The panel can be surface or flush mounted. Refer to Figure 1 for dimensions.

For surface mounting, mark the location of the four mounting holes. Install the top two screws into
the wall and place the panel over the screws. Install the bottom screws, and tighten down all four
screws.

For flush mounting, make the wall cut-out according to the panel dimensions. Remove the control
panel door. Mount the flush mounting trim (MODEL FA-102TRU) to the back box using the screws
and nuts provided with the flush mounting kit. Re-install the door on top of the flush trim. The cam
lock may require a minor adjustment in order to compensate for the flush trim.

3. FUNCTION SELECTION

The following jumpers are available for function selection, refer to Figure 2 for location;

JW1

Cut for normally open trouble contacts.

JW2

Cut for normally closed trouble contacts.

JW3

Cut to enable

common alarm

relay to de-energize if

signal silence

switch is activated.

JW6

Cut if

60 second signal silence

inhibit is not required (Signals can be manually

silenced any time if cut).

JW7

Cut to enable lamp supervision for the remote annunciator alarm zones.

Summary of Contents for FA-1025U

Page 1: ...ecifications contained in this manual are subject to change without prior notice by the manufacturer FA 1025U Fire Alarm Control Panel INSTALLATION and OPERATION MANUAL 1998 by Mircom Technologies Lim...

Page 2: ......

Page 3: ...5 5 BATTERY FAULT LED 3 5 6 GROUND FAULT LED 3 5 7 REMOTE LAMP FAIL LED 3 5 8 SIGNAL TROUBLE LED 3 6 SEQUENCE OF OPERATION 6 1 NORMAL 3 6 2 ALARM 3 6 3 SIGNAL SILENCE 3 6 4 RESET 3 7 SYSTEM CHECKOUT...

Page 4: ......

Page 5: ...l and place the panel over the screws Install the bottom screws and tighten down all four screws For flush mounting make the wall cut out according to the panel dimensions Remove the control panel doo...

Page 6: ...power is connected to the terminal block above the transformer Use GEL CELL or SEALED LEAD ACID type of batteries only Connect the batteries after power up Use 24V 4AH batteries for 24 hours standby...

Page 7: ...MAL All indicators are normally OFF except for the green A C On LED 6 2 ALARM A red zone alarm LED will illuminate steadily for incoming alarm 6 3 SIGNAL SILENCE If the 60 second signal silence inhibi...

Page 8: ...zzer should sound intermittently the common trouble LED flash indicating battery fault 3 Connect the batteries carefully observing the correct polarity 4 The common trouble LED should extinguish If th...

Page 9: ...5 FIGURE 1 BACKBOX FLUSH TRIM MOUNTING DETAILS...

Page 10: ...6 FIGURE 2 CIRCUIT BOARD LAYOUT...

Page 11: ...7 FIGURE 3 DETECTION AND SIGNAL WIRING INSTRUCTION...

Page 12: ...8 FIGURE 4 WIRING TABLE FOR DETECTION ZONE...

Page 13: ...9 FIGURE 5 WIRING TABLE FOR BELLS AND HORNS...

Page 14: ...10 FIGURE 6 ALARM TROUBLE RELAY CONTACTS AND REMOTE ANNUNCIATION WIRING INSTRUCTION...

Page 15: ...00 003 SYSTEM SENSOR PSD 7131 70 201000 005 1400 A PSD 7130 70 201000 001 MIRTONE 2400 A 73471 PSD 7130 70 201000 002 1451 A B401B 73494 PSD 7130 70 201000 003 1451 A B406B 73575 PSD 7130 70 201000 00...

Page 16: ...00 0 10 mA 702E 702U 1451 B401B A A 0 12 mA 712U 701E 701U S10A S00 0 10 mA 702E 702U 1451 B406B A A 0 12 mA 713 5U 701E S10A S00 0 10 mA 701U 702E 702U 1451DH DH400 A A 0 12 mA 713 6U 701E S10A S00 0...

Page 17: ...2475W FR NS4 24110W FR RS 2415W FR RSS 241575W FR RSS 2415W FR RSS 241575W FR RSS 2430W FR RSS 2475W FR RSS 24110W FR RSS 2415C FW RSS 2430C FW RSS 2475C FW RSS 24100C FW MT 12 24 ULC MT 24 LS VFR UL...

Page 18: ...et 2 Sig X 0 114 0 200 RTI 1 Remote Trouble Indicator X 0 035 0 035 2 Wire Smoke Detectors X 0 0001 0 090 0 090 4 Wire Smoke Detectors X Signal Load bells horns strobes and etc Total currents Add abov...

Page 19: ...n repaired by others abused improperly installed altered or otherwise misused or damaged in any way Unless previously contracted by MIRCOM MIRCOM will assume no responsibility for determining the defe...

Page 20: ......

Reviews: