background image

*Note: The BPS-602 will only synchronize horns, horn/strobes and strobes that contain synchronization capability.

  Contact signal manufacturer for more detailed info (see Appendix A.4, pg. 12). The same synchronization mode must be

  selected for all outputs

Amount of Notification Appliances per NAC:

Amseco

27 per NAC*

System Sensor®

32 per NAC*

Faraday

39 per NAC*

CooperWheelock®

32 per NAC*

Gentex®

32 per NAC*

*Not to exceed a maximum of 2.5 amp per NAC.

Terminal Identification Table:

AL800LGK9E Logic Board

 Terminal

 Legend

 Function/Description

 IN1+, IN1-

 IN2+, IN2-

 (Supervised)

These terminals connect to the 24VDC FACP notification appliance circuit outputs.  

 

(Class A, Style Z or Class B, Style W, X, Y) Input trigger voltage is 8-33VDC @ 5mA min. 

Terminal polarity is shown in alarm condition. During an alarm condition these inputs will cause 

the selected outputs chosen to drive notification appliances. The designated outputs are set by output 

switches[OUT1 through OUT4] (Output Programming Selection Table, pg. 4). A trouble condition on 

an output loop will cause the corresponding input to trip the FACP by opening the FACP loop. An 

alarm condition will always override trouble to drive notification appliances.

 RET1+, RET1-

 RET2+, RET2-

 (Supervised)

For (Class A, Style Z hookups these terminal pairs return to FACP NAC1 and/or NAC2. For Class 

B, Style W, X, Y hookups the FACP EOL resistor from the NAC1 and/or NAC2 outputs are 

terminated at these terminals.

C “DRY1” NC 

C “DRY2” NC

(Dry input trigger)

An open across these inputs, will cause the selected outputs chosen to drive notification appliances. 

The designated outputs are set by output switches [OUT1 through OUT4] (Output Programming 
Selection Table, pg. 4).
 Note these inputs are unidirectional and will not report a trouble condition 

to the FACP.

 + OUT1 -- 

 + OUT2 --

 + OUT3 -- 

 + OUT4 -- 

 (Supervised)

Notification appliances are connected to these regulated outputs (see 02 Application Guide pg. 2-4). 

Each power-limited output will supply 2.5 amp. Two (2) outputs may be connected in parallel for a 

maximum NAC output capability of 4 amp. Total supply current is 6.5 amp (see note below). Outputs 

are controlled by designated input 1 [IN1] or input 2 [IN2] (Output Programming Selection 

 C “FAULT” NC

 (Common

 trouble input)

An open circuit across this pair of terminals will cause [IN1 and IN2] to simultaneously signal a 

trouble condition back to the FACP (Typically used to report AC or BAT Fail). (form “C” contact 1 

amp / 28VDC) (Fig. 2, pg. 7).

 NC, C, NO

 (Common

 trouble output)

These are dry contact trouble outputs that follow any general loop/system trouble conditions. 

(Typically used to trigger a digital communicator or other reporting device).

(form “C” contact 1 amp / 28VDC 0.35 Power Factor) (Fig. 2, pg. 7) .

 --  AUX+

This separate 1 amp max auxiliary Special Application Power output circuit is typically used to    

power 4-wire smoke detectors. See attached list of devices (Appendix A, pgs. 10-12).

 + DC -- 

 24VDC from power supply.

Note: Unit is equipped with 1 amp max. auxiliary output: “AUX” will remain battery backed up during power 

outage. For loads connected to “AUX” please refer to battery “Stand-by Specifications” pg. 3 for ratings. When 

loads are connected to “AUX” output during alarm condition, the remaining outputs may not exceed 6.5 amp 

total alarm current (example: AUX = 1 amp, outputs up to 5.5 amp).

 

BPS-602 

- 5 -

Summary of Contents for BPS-602

Page 1: ...Rev 042209 BPS 602 NAC Power Extender Installation Guide see Application Guide for additional information...

Page 2: ...ry helps identify intermittent loop problems Common trouble input and output for external trouble signals tie in Ground fault detection Unit includes power supply red enclosure cam lock and battery le...

Page 3: ...ection Table pg 4 Sync Mode Selection Table pg 4 Terminal Identification Table pgs 5 6 LED Status Indication Table pg 6 1 Mount unit in the desired location Mark and predrill holes in the wall to line...

Page 4: ...provide a means of synchronizing the Temporal coded horns synchronizing the flash timing of the strobe and silencing the horns of the horn strobe combination over a two wire circuit while leaving str...

Page 5: ...sen to drive notification appliances The designated outputs are set by output switches OUT1 through OUT4 Output Programming Selection Table pg 4 Note these inputs are unidirectional and will not repor...

Page 6: ...ds Low battery condition will report at approximately 21VDC Battery presence detection will report with in 180 seconds after battery remains undetected missing or removed A restored battery will repor...

Page 7: ...NC OUT1 OUT3 OUT2 OUT4 INPUT SELECT TEMPORAL STROBE SYNC IN OUT SYNC IN1 IN1 IN2 IN2 C DRY1 NC RET1 RET1 RET2 RET2 C DRY2 NC OUT2 OUT3 OUT4 INPUT SELECT TEMPORAL STROBE SYNC IN OUT SYNC AUX UPPER TERM...

Page 8: ...nnect to the host control panel for local annunciation of the trouble condition Note If common trouble input terminals marked C FAULT NC are not used these terminals must be shorted connect jumper to...

Page 9: ...mA Alarm mA 0mA mA Alarm mA 0mA mA Alarm mA 0mA mA C Notification Appliances Current must not exceed 6 5 amp 6500mA 0mA mA D Total alarm current mA mA E Total current ratings converted to amperes lin...

Page 10: ...sor DH400ACDCI Ionization Duct 25 95 System Sensor DH400ACDCP Photoelectric Duct 25 95 System Sensor 1112 24 D Ionization 0 05 50 System Sensor 1424 Ionization 0 10 41 System Sensor 1451 w B402B Base...

Page 11: ...05 System Sensor 6424 Projected Beam 10 28 4 System Sensor Beam 1224 S Projected Beam 17 38 5 Contact manufacturer for current draws A 2 Door Holders Table A 2 below lists door holders compatible with...

Page 12: ...CW RSSP 24150W RSSP 24177W RSSP 24185W STW Appliances with Sychronizing Strobes AMT 241575W AMT 2475W AMT 241575W NYC AMT 2475W NYC MT 12575W MT 241575W MTWP 2475W CH70 24MCW CH70 24MCC CH70 2415C CH7...

Page 13: ...MB G10 24 MIZ TC24 Gentex Devices Models GE3 Series GES GEC Series GCS GCC Series SSPK Wall and Ceiling Mount Series GX93 Series WGE and color lense units System Sensor Devices Wall Horn Strobes P2R P...

Page 14: ...SET HMC W SET S17R WP SET S17 W WP SET S17 CW WP SET MC CW SET MC CR SET HMC CW SET HMC CR SET 177 CR WP SET 177 CW WP SET 185 R WP SET 185 W WP SEF MC R SEF MC W SEF HMC R SEF HMC W SEF MC CW SEF HM...

Page 15: ...BPS 602 15 Notes...

Page 16: ...31 75mm 1 1 27 94mm 1 1 27 94mm 0 79 20 06mm 1 1 27 94mm 0 91 23 114mm 0 91 23 114mm 1 375 34 925mm 1 125 28 575mm 15 5 393 7mm 4 615 117 22mm 12 23 310 64mm 4 615 117 22mm 1 5 38 1mm 1 5 38 1mm 4 61...

Reviews: