BPS-602 

- 3 -

Power Supply Specifications:

AC Input:

120VAC 60Hz, 4 amp.

Output:

Four (4) regulated supervised NAC output circuits, 24VDC, 2.5 amp maximum current. 

One (1) aux. special application 24VDC power output circuit 1 amp, non-supervised 

total output current must not exceed current 6.5 amp in Alarm Condition.

Battery

Use two (2) 12VDC / 7AH, two (2) 12VDC / 12AH or two (2) 12VDC / 40AH

batteries connected in series.

Stand-by/Alarm Current 

Consumption:

90mA/175mA

EOL Resistor (end of line):

2.2K (2200 ohm).

Ground fault maximum

test impedance:

1000 ohm.

Stand-by Specifications:

Stand-by  Batteries  

Stand-by Time Total Amp/Minutes Alarm Output Current Aux. Output

24VDC/7AH

24 Hours

6.5 amp/5 minutes

---

24VDC/12AH

(use two (2) 12VDC batteries in series)

24 Hours

6.5 amp/5 minutes

50mA

24VDC/40AH

24 Hours

6.5 amp/5 minutes

1 amp

Note: Unit is equipped with 1 amp max. auxiliary output: “AUX” will remain battery backed up during power
outage. For loads connected to “AUX” please refer to battery “Stand-by Specifications” above for ratings. When 
loads are connected to “AUX” output during alarm condition, the remaining outputs may not exceed 6.5 amp 
total alarm current (example: AUX = 1 amp, outputs up to 5.5 amp).

Installation Instructions:

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all local 

codes and authorities having jurisdiction.

Product is intended for indoor dry use only. 

 

Carefully review:

 

Application Guide for BPS-602, BPS-802, BPS-1002

 

Power Supply Specifications 

(pg. 3)

 

Stand-by Specifications 

(pg. 3) 

 

Output Programming Selection Table 

(pg. 4)

 

Sync Mode Selection Table 

(pg. 4)

 

Terminal Identification Table 

(pgs. 5-6)

 

LED Status Indication Table 

(pg. 6)

1.   Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the  

 

 

enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s    

 

upper keyholes over the two upper screws; level and secure. Mark the position of the lower two holes. Remove the    

 

enclosure. Drill the lower holes and install two fasteners. Place the enclosure’s upper keyholes over the two upper    

 

screws. Install the two lower screws and make sure to tighten all screws (Enclosure Dimensions, pg. 12)

 

Secure enclosure to earth ground (Fig. 1, pg. 3). Small terminal block wire gauges range from 

 

16 AWG to 24 AWG, all others range from 14 AWG to 24 AWG.

2.  Connect the line (L) and neutral (N) terminals to a separate unswitched AC circuit (120VAC, 60Hz)

 

dedicated to the Fire Alarm System. 

3.  Measure output voltage before connecting devices. This helps avoiding potential damage.

4.  Connect battery to the terminals marked [+ BAT - ] on the Power Supply Board (battery leads included). 

 

Use two (2) 12VDC batteries connected in series. 

5.  Set output selection switches marked [OUT1 through OUT4] to follow corresponding input [IN1 & IN2] and 

 

desired output signal type (Output Programming Selection Table, pg. 4).

6.  Connect FACP output to the desired AL800LGK9E logic board inputs, and notification appliances to the desired  

 

 

AL800LGK9E logic board outputs (see 02 Application Guide).

 

Note: The 2-wire horn/strobe sync mode will only synchronize horns, horn/strobes, strobes with 

 

synchronization capability.

7.  For connection of smoke detectors, digital dialer see Hookup Diagram, pg. 7.

Fig. 1

L       N

line 

ground

neutral

Summary of Contents for BPS-602

Page 1: ...Rev 042209 BPS 602 NAC Power Extender Installation Guide see Application Guide for additional information...

Page 2: ...ry helps identify intermittent loop problems Common trouble input and output for external trouble signals tie in Ground fault detection Unit includes power supply red enclosure cam lock and battery le...

Page 3: ...ection Table pg 4 Sync Mode Selection Table pg 4 Terminal Identification Table pgs 5 6 LED Status Indication Table pg 6 1 Mount unit in the desired location Mark and predrill holes in the wall to line...

Page 4: ...provide a means of synchronizing the Temporal coded horns synchronizing the flash timing of the strobe and silencing the horns of the horn strobe combination over a two wire circuit while leaving str...

Page 5: ...sen to drive notification appliances The designated outputs are set by output switches OUT1 through OUT4 Output Programming Selection Table pg 4 Note these inputs are unidirectional and will not repor...

Page 6: ...ds Low battery condition will report at approximately 21VDC Battery presence detection will report with in 180 seconds after battery remains undetected missing or removed A restored battery will repor...

Page 7: ...NC OUT1 OUT3 OUT2 OUT4 INPUT SELECT TEMPORAL STROBE SYNC IN OUT SYNC IN1 IN1 IN2 IN2 C DRY1 NC RET1 RET1 RET2 RET2 C DRY2 NC OUT2 OUT3 OUT4 INPUT SELECT TEMPORAL STROBE SYNC IN OUT SYNC AUX UPPER TERM...

Page 8: ...nnect to the host control panel for local annunciation of the trouble condition Note If common trouble input terminals marked C FAULT NC are not used these terminals must be shorted connect jumper to...

Page 9: ...mA Alarm mA 0mA mA Alarm mA 0mA mA Alarm mA 0mA mA C Notification Appliances Current must not exceed 6 5 amp 6500mA 0mA mA D Total alarm current mA mA E Total current ratings converted to amperes lin...

Page 10: ...sor DH400ACDCI Ionization Duct 25 95 System Sensor DH400ACDCP Photoelectric Duct 25 95 System Sensor 1112 24 D Ionization 0 05 50 System Sensor 1424 Ionization 0 10 41 System Sensor 1451 w B402B Base...

Page 11: ...05 System Sensor 6424 Projected Beam 10 28 4 System Sensor Beam 1224 S Projected Beam 17 38 5 Contact manufacturer for current draws A 2 Door Holders Table A 2 below lists door holders compatible with...

Page 12: ...CW RSSP 24150W RSSP 24177W RSSP 24185W STW Appliances with Sychronizing Strobes AMT 241575W AMT 2475W AMT 241575W NYC AMT 2475W NYC MT 12575W MT 241575W MTWP 2475W CH70 24MCW CH70 24MCC CH70 2415C CH7...

Page 13: ...MB G10 24 MIZ TC24 Gentex Devices Models GE3 Series GES GEC Series GCS GCC Series SSPK Wall and Ceiling Mount Series GX93 Series WGE and color lense units System Sensor Devices Wall Horn Strobes P2R P...

Page 14: ...SET HMC W SET S17R WP SET S17 W WP SET S17 CW WP SET MC CW SET MC CR SET HMC CW SET HMC CR SET 177 CR WP SET 177 CW WP SET 185 R WP SET 185 W WP SEF MC R SEF MC W SEF HMC R SEF HMC W SEF MC CW SEF HM...

Page 15: ...BPS 602 15 Notes...

Page 16: ...31 75mm 1 1 27 94mm 1 1 27 94mm 0 79 20 06mm 1 1 27 94mm 0 91 23 114mm 0 91 23 114mm 1 375 34 925mm 1 125 28 575mm 15 5 393 7mm 4 615 117 22mm 12 23 310 64mm 4 615 117 22mm 1 5 38 1mm 1 5 38 1mm 4 61...

Reviews: