background image

17

16

English

Battery Type

24VDC

Typical Recharge Time

BP24RTEXL

Model Number

SYSTEM SPECIFICATIONS

Format

Rack/Tower Convertible

BATTERY SYSTEM

Typical Battery Life

System Current

40 Amps

20 - 12V9.0Ah

Battery Qty/Rating

BP72RTEXL

System Voltage

Sealed, Non-Spillable, Maintenance Free, Value Regulated, Lead Acid

3-5 years, depending on discharge cycles and ambient temperature

24-hours from total discharge

72VDC

PHYSICAL

Weight - Net

Size - Net
L X W X H

Size - Shipping
L X W X H

Weight - Shipping

26.8 x 17.3 x 5.2"
680 x 440 x 132 mm

35.8 x 22.0 x 10.7"
909 x 560 x 272 mm

148.2 lbs
67.2 Kgs

138.9 lbs
63.0 Kgs

 BP48RTEXL

48VDC

127.9 lbs
58.0 Kgs

137.1 lbs
62.2 Kgs

ENVIRONMENTAL

Operating Temperature

Operating/Storage
Humidity

Operating Elevation

0 to 40

°

C (+32 to +104

°

F)

95% Non-Condensing

0 to 3,000m (0 to +10,000 ft)

Storage Elevation

0 to 15,000m (0 to +50,000 ft)

Storage Temperature

-15 to +45

°

C (+5 to +113

°

F)

 BP36RTEXL

36VDC

18 - 12V9.0Ah

6. SPECIFICATIONS

English

IF THE UPS REQUIRES SERVICE

1. Use the TROUBLESHOOTING section to eliminate obvious causes.
2. Verify there are no circuit breakers tripped.  A tripped circuit breaker is the

  most common problem.

3. Call your dealer for assistance.  If you cannot reach your dealer, or if they

  cannot resolve the problem call or fax MINUTEMAN Technical Support at the
  following numbers; Voice phone (972) 446-7363, FAX line (972) 446-9011 or
  visit our Web site at www.minutemanups.com the "Discussion Board".  Please
  have the following information available BEFORE calling the Technical Sup-
  port Department.
 A. Your name and address.
 B. Where and when the unit was purchased.
 C. All of the model information about your Battery Pack and UPS.
 D. Any information on the failure, including LEDs that may be illuminated.
 E. A description of the protected equipment, including model numbers if

 possible.

 F. A technician will ask you for the above information and, if possible, help

 solve your problem over the phone.  In the event that the unit requires fact-
 ory service, the technician will issue you a Return Material Authorization
 Number (RMA #).

 G. If the Battery Pack is under warranty, the repairs will be done at no charge.

 If not, there will be a charge for repair.

4. Pack the Battery Pack in its original packaging.  If the original packaging is

 no longer available, ask the Technical Support Technician about obtaining a
 new set.  It is important to pack the Battery Pack properly in order to avoid
 damage in transit. Never use Styrofoam beads for a packing material.
 A. Include a letter with your name, address, day time phone number, RMA

  number, a copy of your original sales receipt, and a brief description of the
  problem.

5. Mark the RMA # on the outside of all packages.  The factory cannot accept

 any package without the RMA # marked on the outside.

6. Return the Battery Pack by insured, prepaid carrier to:

Para Systems Inc.
MINUTEMAN UPS

1455 LeMay Drive

Carrollton, TX 75007

ATTN: RMA # _______

5. OBTAINING SERVICE

Summary of Contents for BP24RTEXL

Page 1: ... s Manual Rack Tower Extended Runtime Battery Packs Para Systems Inc 1455 Lemay Dr Carrollton TX 75007 Phone 1 972 446 7363 Fax 1 972 446 9011 Internet minutemanups com UPS Sizing sizemyups com P N 34000424 ...

Page 2: ... Copyright 2011 English 1 Introduction 2 2 Controls and Indicators 6 3 Installation 7 4 Replacing the Battery 12 5 Obtaining Service 16 6 Specifications 17 7 Limited Product Warranty 18 TABLE OF CONTENTS ...

Page 3: ...nd place of purchase if any damage is found Warranty claims for damage caused by the carrier will not be honored The packing materials that your Battery Pack was shipped in are carefully designed to minimize any shipping damage In the unlikely case that the Battery Pack needs to be returned to the manufac turer please use the original packing material Since the manufacturer is not responsible for ...

Page 4: ... where failure or malfunction of the product can be reason ably expected to cause failure of the life support device or to significantly affect its safety or effectiveness We do not recommend the use of any of our prod ucts in direct patient care We will not knowingly sell our products for use in such applications unless it receives in writing assurances satisfactory to us that a the risks of inju...

Page 5: ...he Battery Pack Place the Battery Pack in the final desired location and complete the rest of the installation procedure WARNING These Battery Packs are extremely heavy Any time the Battery Pack has to be handled be sure to use enough person nel strong supports and equipment to safely handle the Battery Pack ENVIRONMENTAL Operating Temperature max Operating Storage Humidity Operating Elevation 0 t...

Page 6: ... mounting brackets and rails for the standard 19 46 5cm 4 post rack The screws for mounting the Battery Pack to the rack are not included screw size varies with rack size 1 Mount the rails to the 4 post rack FIG 1 2 Locate the mounting bracket screw holes on the side panels of the Battery Pack at the front of the Battery Pack FIG 2 3 Align the mounting bracket with the mounting bracket screw holes...

Page 7: ...us voltage for the Battery Packs CONNECTING THE BATTERYPACK QUALIFIED SERVICE PERSONNELONLY NOTE When using these Battery Packs the UPS must be configured so that the UPS will report the correct estimated runtime in the SentryPlus software or the SNMP card and to make the Battery capacity bar graph LEDs display properly See the SentryPlus software or the SNMP NET card User s Manual to configure th...

Page 8: ...e operated vents These Battery Packs contain sealed non spillable maintenance free lead acid batteries CAUTION Yuasa Part REW45 12 CSB Part HR 1234W F2 18 12V9 0Ah English WARNING This Battery Pack contains potentially hazardous voltages Do not attempt to disassemble the Battery Pack beyond the battery replacement procedure These Battery Packs contain no user serviceable parts Repairs and Battery ...

Page 9: ...d and black NOTE Some sparking might occur this is normal 31 Re install the battery retaining bracket FIG 5 32 Re install the retaining screws for the battery retaining bracket FIG 5 33 Re install the front panel on the Battery Pack 34 Re install the front panel retaining screws FIG 6 35 Re install the front panel retaining screw cover plates FIG 7 36 Reconnect all of the external battery cables 3...

Page 10: ...972 446 9011 or visit our Web site at www minutemanups com the Discussion Board Please have the following information available BEFORE calling the Technical Sup port Department A Your name and address B Where and when the unit was purchased C All of the model information about your Battery Pack and UPS D Any information on the failure including LEDs that may be illuminated E A description of the p...

Page 11: ...fter delivery in regard to use or application of Para Systems s equipment is furnished without charge and on the basis that it represents Para Systems s best judgment under the circumstances but it is used at the recipient s sole risk EXCEPTAS PROVIDED HEREIN PARA SYSTEMS MAKES NO WARRANTIES EX PRESSED OR IMPLIED INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE Some sta...

Reviews: