17
16
English
Battery Type
24VDC
Typical Recharge Time
BP24RTEXL
Model Number
SYSTEM SPECIFICATIONS
Format
Rack/Tower Convertible
BATTERY SYSTEM
Typical Battery Life
System Current
40 Amps
20 - 12V9.0Ah
Battery Qty/Rating
BP72RTEXL
System Voltage
Sealed, Non-Spillable, Maintenance Free, Value Regulated, Lead Acid
3-5 years, depending on discharge cycles and ambient temperature
24-hours from total discharge
72VDC
PHYSICAL
Weight - Net
Size - Net
L X W X H
Size - Shipping
L X W X H
Weight - Shipping
26.8 x 17.3 x 5.2"
680 x 440 x 132 mm
35.8 x 22.0 x 10.7"
909 x 560 x 272 mm
148.2 lbs
67.2 Kgs
138.9 lbs
63.0 Kgs
BP48RTEXL
48VDC
127.9 lbs
58.0 Kgs
137.1 lbs
62.2 Kgs
ENVIRONMENTAL
Operating Temperature
Operating/Storage
Humidity
Operating Elevation
0 to 40
°
C (+32 to +104
°
F)
95% Non-Condensing
0 to 3,000m (0 to +10,000 ft)
Storage Elevation
0 to 15,000m (0 to +50,000 ft)
Storage Temperature
-15 to +45
°
C (+5 to +113
°
F)
BP36RTEXL
36VDC
18 - 12V9.0Ah
6. SPECIFICATIONS
English
IF THE UPS REQUIRES SERVICE
1. Use the TROUBLESHOOTING section to eliminate obvious causes.
2. Verify there are no circuit breakers tripped. A tripped circuit breaker is the
most common problem.
3. Call your dealer for assistance. If you cannot reach your dealer, or if they
cannot resolve the problem call or fax MINUTEMAN Technical Support at the
following numbers; Voice phone (972) 446-7363, FAX line (972) 446-9011 or
visit our Web site at www.minutemanups.com the "Discussion Board". Please
have the following information available BEFORE calling the Technical Sup-
port Department.
A. Your name and address.
B. Where and when the unit was purchased.
C. All of the model information about your Battery Pack and UPS.
D. Any information on the failure, including LEDs that may be illuminated.
E. A description of the protected equipment, including model numbers if
possible.
F. A technician will ask you for the above information and, if possible, help
solve your problem over the phone. In the event that the unit requires fact-
ory service, the technician will issue you a Return Material Authorization
Number (RMA #).
G. If the Battery Pack is under warranty, the repairs will be done at no charge.
If not, there will be a charge for repair.
4. Pack the Battery Pack in its original packaging. If the original packaging is
no longer available, ask the Technical Support Technician about obtaining a
new set. It is important to pack the Battery Pack properly in order to avoid
damage in transit. Never use Styrofoam beads for a packing material.
A. Include a letter with your name, address, day time phone number, RMA
number, a copy of your original sales receipt, and a brief description of the
problem.
5. Mark the RMA # on the outside of all packages. The factory cannot accept
any package without the RMA # marked on the outside.
6. Return the Battery Pack by insured, prepaid carrier to:
Para Systems Inc.
MINUTEMAN UPS
1455 LeMay Drive
Carrollton, TX 75007
ATTN: RMA # _______
5. OBTAINING SERVICE