30
Enter main
menu
When displaying default UPS status
summary screen, press this button for
>1s to enter the main menu tree
Exit main
menu
Press this button for >1s to exit the
present menu to default system status
display menu without executing a
command or changing a setting
Scroll up
Press this button for >100ms&<1s to
scroll up the menu option
Scroll down
Press this button for >100ms&<1s to
scroll down the menu option
Enter next
menu tree
Press this button for >100ms&<1s to
select the present menu option, or enter
next menu, but do not change any
setting
Select one
menu
option
Press this button for >100ms&<1s to
select the present menu option, or enter
next menu, but do not change any
setting
Confirm the
present
setting
Press this button for >1s to confirm the
edited options and change the setting
Table 5-2 Buzzer definition
UPS condition
Buzzer status
Fault active
Continuous
Warning active
Beep every second
Battery output
Beep every 4 seconds, if battery low, buzzer Beep
every second
Bypass output
Beep every 2 minutes
The UPS provides useful information about UPS itself, load status,
events, measurements, identification, and settings through the front
panel display.
Summary of Contents for 6-10KVA Tower
Page 1: ...USER MANUAL ONLINE UPS 6 10KVA Rack Tower ...
Page 24: ...21 Frequency converter without Bypass AC input ...
Page 31: ...28 Figure 26 Parallel systerm wiring diagram of 6K 10K ...
Page 40: ...37 Fig 5 14 Main menu tree ...
Page 47: ...44 Example set rated output voltage value Fig 5 22 Set rated output voltage value ...
Page 61: ...58 614 08090 00 ...