4 Installation and connection information
4.1 General information
-
Only use the cable glands provided by the manufacturer.
-
Install the junction box so that the cable glands are on the bottom.
-
Do not open the junction box when connected to the voltage supply.
Note:
At ambient temperatures >45°C, cables that are suitable for at least 85°C must be used.
4.2 Terminals and jumpers
Terminal contacts
1–4
+ measuring voltage (load cells)
green
Terminal contact
IND
+ measuring voltage (connection cable)
Terminal contacts
1–4
- measuring voltage (load cells)
Signal -
gray
Terminal contact
IND
- measuring voltage (connection cable)
Terminal contacts
1–4
- supply voltage (load cells)
Supply -
blue
Terminal contact
IND
- supply voltage (connection cable)
4 Installation and connection information
Cable Junction Box PR 6130/34Sa
Minebea Intec
EN-11