Function number 24
Limit 2 on
Function number 25
Limit 2 off
Function number 26
Limit 3 on
Function number 27
Limit 3 off
7.2.5.12
Function number 30, 31: Fixed values (Read/Write)
Function number 30
Fixed value for analog output, value (num) 0
20000 corre-
sponds to 20 mA
Function number 31
Fixed value for preset tare, see also
SetFixTare
,
GetFixTare
in Chapter
7.2.5.13
Function number 80…93: state-controlled action bits (write)
Note:
For setting bits, see Chapter
.
Only setting and resetting of single bits is possible.
When changing a bit from 0 to 1, the corresponding action starts. After handling the
command, the bit must be reset. Application: The master writes cyclically.
The bit is set as
Write_Value_Select
with the specified number (see Chapter
).
The bit is reset at the specified 128.
Function number 80
SetZero
Set the gross weight to zero.
Function number 81
SetTare
The weighing point is tared.
Function number 82
ResetTare
Reset tare.
Function number 83
SetTest
Start the ADC test.
Function number 84
ResetTest
Finish the ADC test.
Function number 85
ResetPwf
Reset the
PowerFail
bit (function num-
ber 1; the bit was set after "power on").
Function number 86
SetFixTare
Taring with weight in numerical address
D31 "FixTare".
Function number 87
GetFixTare
The current gross weight is copied to
the numerical address D31.
Function number 89
ResetError
The
CmdError
error bit is reset.
Function number 90
SaveProcess
The process data are saved in EAROM.
Limits (function number 22…27)
Fixed analogue output value (function
number 30)
Preset tare (function number 31)
7 ProfiBus interface
Transmitter Series PR 5211
EN-71
Minebea Intec