background image

 

 

ZIEHL  industrie 

– elektronik  GmbH  + Co  KG 

Daimlerstraße 13,  D 

– 74523 Schwäbisch Hall 

+ 49 791 504-0,   [email protected],   www.ziehl.de 

 
 

 

Temperature Relays and MINIKA® 

Mains Monitoring 

Digital Panelmeters MINIPAN® 

Switching Relays and Controls 

Measuring Transducers 

Grid- and Plant Protection 

 

Operating Manual MU1001K

 

updated: 2018-11-12 / sm 

from Firmware: 0-04

 

 

 

 

MU1001K 

12370-0707-01 

Seite

 

1 / 12 

www.ziehl.de 

- Measuring-Transducer 

 
 
 

 

 
 
 
 

   

 

 

 

Summary of Contents for MU1001K

Page 1: ...l de www ziehl de Temperature Relays and MINIKA Mains Monitoring Digital Panelmeters MINIPAN Switching Relays and Controls Measuring Transducers Grid and Plant Protection Operating Manual MU1001K updated 2018 11 12 sm from Firmware 0 04 MU1001K 12370 0707 01 Seite 1 12 www ziehl de Measuring Transducer ...

Page 2: ...iew of commissioning 5 6 2 Overview of the predefined standard ranges 5 6 3 Setting a predefined range 6 6 4 Diagram for setting a predefined range 7 6 5 Overview of scaling an arbitrary range 8 6 6 Scaling of range 8 6 7 Diagram for scaling of range 9 6 8 Factory setting 10 6 9 Query of firmware version 10 6 9 1 Revision Firmware 10 7 Maintenance and repair 10 8 Error search 10 9 Technical data 1...

Page 3: ... supply AC DC 24 240 V the measuring transducer can be connected to all common supply voltages 2 Overview of functions Output signal 0 20mA and 0 10V or 4 20mA and 2 10V Rated Supply Voltage AC DC 24 240V Insulation between inputs outputs and supply voltage Standard ranges adjustable universally scalable input ranges Inputs DC 300 300 mV preset values 0 60 0 150 0 300 60 60 150 150 300 300 mV DC 1...

Page 4: ...afety instructions in this instruction manual titled Important Information Failure to follow the safety instructions may result in death personal injury or property damage to the equipment itself and other equipment and facilities Instead of the industrial norms and regulations written in this instruction manual valid for Europe you must observe out of their geographical scope the valid and releva...

Page 5: ...least 300 Vac 6 Commissioning 6 1 Overview of commissioning The MU1001K can be commissioned to predefined standard ranges or scaled to an arbitrary range There are two different ways to do the settings Point 6 2 6 4 MU1001K setting a predefined range Point 6 5 6 7 MU1001K scaling an arbitrary range 6 2 Overview of the predefined standard ranges Following standard ranges can be set without adjustme...

Page 6: ... 1 x 0 20 V 0 10 V 0 60 mV 2 x 0 50 V 2 10 V 0 150 mV 3 x 0 100 V 10 10 V 0 300 mV 4 x 0 200 V 60 60 mV 5 x 0 300 V 150 150 mV 300 300mV Press button Down Parameterization output LED Power flashes 4x Select with button Set the output range Number of LED flashes 10 V mV 1 x 0 10V 0 20mA 2 x 2 10V 4 20mA Press button Down End of parameterization LED ON lights permanently Attention When no button is ...

Page 7: ...MU1001K 12370 0707 01 Seite 7 12 www ziehl de 6 4 Diagram for setting a predefined range Mode Normal state Parameterization mode ...

Page 8: ...Power flashes 2x Connect a signal at the input corresponding to the zero point Press button Down store of value green LED flashes 3 times quickly Parameterization input full scale LED Power flashes 3x Connect a signal at the input corresponding to the full scale Press button Down store of value green LED flashes 3 times quickly Parameterization output LED Power flashes 4x Select with button Set th...

Page 9: ...MU1001K 12370 0707 01 Seite 9 12 www ziehl de 6 7 Diagram for scaling of range Signal input Zero point Signal input Full scale Mode Normal state Parameterization mode ...

Page 10: ...ion Firmware Version 0 04 additional predefined standard ranges 10 10V 60 60mV 150 150mV 300 300mV 7 Maintenance and repair ZIEHL industrie elektronik GmbH Co KG Daimlerstr 13 D 74523 Schwaebisch Hall Phone 49 791 504 0 Fax 49 791 504 56 E Mail info ziehl de Homepage www ziehl com 8 Error search Wrong output signal current voltage OUT terminal 1 2 3 Cause The device is not configured correctly Rem...

Page 11: ...ution 11 6 Bit 3 1 mV Load 1 k Ω Current output DC 0 4 20 mA Tolerance 0 3 of full scale from 0 1 mA Temperature factor 0 015 K Resolution 11 6 Bit 6 1 µA Load 500 Ω Error from load 250 Ω resistance 250 Ω 0 3 of final value Galvanic insulation Us input output Test voltage Us output DC 3540V Us input DC 3540V Input output DC 3540V Test conditions EN 61010 1 Rated supply voltage Us terminals A1 A2 P...

Page 12: ...ture 5 C 70 C Climatic conditions 5 85 rel humidity no condensation Installation height 2000 m Vibration resistance EN 60068 2 6 2 25 Hz 1 6 mm 25 150 Hz 5 g Housing Type K Dimension H x W x D 75 x 22 5 x 115 mm Width 1 TE Line connection solid wire each 1 x 0 5 2 5 mm2 Stranded wire with insulated ferrules each 1 x 0 14 1 5 mm2 Torque 0 5 Nm 3 6 lb in Protection class housing terminals IP 40 IP 2...

Reviews: