SAMPLE WORKSHEET 2 (see page 14)
CT124 SETUP WORKSHEET
Use this worksheet to describe the setup parameters for the desired operation of the CT124.
Fill in a short description of the location and purpose of each temperature sensor, and save the worksheet for future reference.
Basic function description:
Monitor motor windings & bearings
Description of Zones
Description of Relay Functions
Trip Temp.
Zone 1:
Stator #1
Relay 1:
Stator overtemp alarm
140°C
Zone 2:
Stator #2
Relay 2:
Stator shutdown
155°C
Zone 3:
Stator #3
Relay 3:
Bearing overtemp alarm
100°C
Zone 4:
Bearing #1
Relay 4:
Bearing shutdown
110°C
Zone 5:
Bearing #2
Zone 6:
---
Alarm only:
---
Zone 7:
---
Zone 8:
---
Completed by:
BFJ
Date:
9/87
Circle the option desired. If the box is empty, fill in a number within the range given at the left. If shaded, there is no option to choose.
DISPLAY
Code
Description
dS
Temperature scale
°F, °C
dC
Zone to be displayed during normal operation:
Highest zone
Lowest zone
Any selected zone
HI
LO
AnY
OUTPUTS - RELAYS AND ALARM
Relay 1
Relay 2
Relay 3
Relay 4
Alarm
rt or At
Trip temperature: -40 to 482°F, -40 to 250°C (to 530°C or 986°F
with Platinum RTD) or "OFF" if the output will not be used
140
155
100
110
OFF
rH or AH
Hysteresis (deadband): 2 to 20 °C or °F
2
2
2
2
rP or AP
Trip on overtemperature (HI)
or undertemperature (LO)
HI
LO
HI
LO
HI
LO
HI
LO
HI
LO
rA
Sound audible alarm when this relay trips?
YES no
YES no
YES no
YES no
rS
Return this relay to normal when silence is pressed?
YES no
YES no
YES no
YES no
AS
Length of alarm silence: 1 to 60 minutes, "---" for stays off.
10
rd or Ad
Trip this output during diagnostic test?
YES no
YES no
YES no
YES no
ro or Ao
Effect of override button on output:
No effect
Trip
Untrip
no
On
OFF
no
On
OFF
no
On
OFF
no
On
OFF
no
OFF
INPUT ZONES
Zone
Scan
Relay 1
Relay 2
Relay 3
Relay 4
Alarm
Sc.
First Column:
Zones to be scanned:
YES = scanned
no = locked out
Remaining columns:
Outputs which respond to each zone:
YES = Output will trip on zone temperature
no = Output not tied to that zone
1
YES no
YES no
YES no
YES no
YES no
YES no
r. or A.
2
YES no
YES no
YES no
YES no
YES no
YES no
3
YES no
YES no
YES no
YES no
YES no
YES no
4
YES no
YES no
YES no
YES no
YES no
YES no
5
YES no
YES no
YES no
YES no
YES no
YES no
6
YES no
YES no
YES no
YES no
YES no
YES no
7
YES no
YES no
YES no
YES no
YES no
YES no
8
YES no
YES no
YES no
YES no
YES no
YES no
CALIBRATION
CAL.
Press DONE unless you wish to recalibrate. See p. 20 of the Instruction Manual.
Minco Products, Inc.
CT124 Instruction Manual
16