THB & TLB
Oil Furnaces
–
Furnace Manual
8
670-000-005/1010
3
Connect supply and return ducts
Duct sizing
Determine air flow CFM
The temperature rise through the furnace must not exceed 85
o
F and
should be at least 55
o
F for comfort. When calculating air flow,
assume a temperature rise of 70
o
F.
The sensible heat temperature change for cooling would be
approximately 27-30
o
F. Actual temperature change will be
approximately 18-21
o
F due to humidity of the air.
To calculate the sensible heat temperature change (
Δ
T), you can
use the formula:
Δ
T = BTU/h/(1.1 x CFM)
Eq. 3-1
To calculate air flow when you know temperature change (
Δ
T), you
can use:
CFM = BTU/h/(1.1 x
Δ
T) Eq.
3-2
You can estimate air flow using the following rules of thumb:
Heating:
14 CFM per 1,000 BTU/h
output
Eq. 3-3
Cooling:
400 CFM per ton
air conditioning
Eq. 3-4
Determine the required air flow based on whichever is larger –
heating mode or air conditioning mode.
Examples:
1.
What would the temperature rise be for a 100,000 BTU/h output
furnace with an air flow rate of 1,200 CFM?
Use Equation 3-1 since you know CFM and BTU/h:
Δ
T = 100,000/(1.1 x 1200) = 76
o
F
•
The temperature rise would be 76
o
F.
•
If the air enters the furnace at 70
o
F, it would leave the
furnace at 70
o
F + 76
o
F = 146
o
F.
2.
What would the air flow be to obtain a 70
o
F rise through a
120,000 BTU/h output furnace?
Use equation 3-2 since you know
Δ
T and BTU/h:
CFM = 120,000/(1.1 x 70) = 1,558 CFM
•
The air flow would have to be 1,558 CFM to obtain a
temperature rise of 70
o
F.
3.
Estimate the required air flow for a 75,000 BTU/h output furnace
installed with a 2-ton air conditioning evaporator coil.
Heating mode air flow (use Equation 3-3):
CFM = 75 x 14 = 1,050 CFM
Cooling mode air flow (use Equation 3-4):
CFM = 2 x 400 = 800 CFM
•
The larger number is 1,050 CFM (heating), so the duct
system should be sized for 1,050 CFM.
•
The supply duct would need to be 16" round or a rectangular
equivalent such as 8" x 25" or 12" x 16", using Table 4,
page 9.
4.
Estimate the required air flow for the same furnace installed with
a 4-ton air conditioning evaporator coil.
Heating mode air flow is still 1,050 CFM.
Cooling mode air flow (use Equation 3-4):
CFM = 4 x 400 = 1,600 CFM
•
The larger number is 1,600 CFM (cooling), so the duct
system should be sized for 1,600 CFM.
•
The supply duct would need to be 18" round or a rectangular
equivalent such as 8" x 36" or 12" x 21", using Table 4,
page 9.
Always check the size of existing ducts, particularly
if you are adding air conditioning. The air pressure
loss through the cooling evaporator coil reduces
available air flow. If the ducts are too small as well,
the system may not work satisfactorily on either
heating or cooling.
Determine duct dimensions
Table 4, page 9, and Table 5, page 10, provide typical round and
rectangular duct sizes for rectangular and flat oval galvanized ducts.
Do not apply these tables to size ductwork if the total equivalent
length of the duct exceeds approximately 100 feet. For longer
systems or for duct board, fiberglass-lined or flexible duct sizing, use
the ACCA Manual D or the ACCA duct sizing slide rule. These
tables are based on pressure loss of approximately 0.10 inch water
column per 100 feet equivalent length of duct.
Use Table 3 below to size or check sizing of takeoffs to supply
registers or return grills.
Verify the size and type of registers, diffusers and grills from the
manufacturer’s ratings. Do not exceed the recommended flow rate.
The pressure drop allowance for each should not exceed
approximately 0.05 inch water column.
Install a return air filter, sized per specifications on Section 12.
Use only a return air filter mounted to the furnace. Do not add
additional filters unless the duct system is carefully sized to allow for
the additional pressure drop.
Table 3
Suggested maximum flow to takeoffs
TAKE-OFF SIZE
(Inches)
SUPPLY
RETURN
5 Round
60
45
6 Round
100
75
7 Round
140
110
8 Round
210
160
3 ¼ x 8 Stack
70
55
3 ¼ x 10 Stack
100
75
3 ¼ x 14 Stack
140
110
2 ¼ x 12 Stack
70
55
2 ¼ x 14 Stack
90
70
6 Round
55
40
8 Round
120
90
10 Round
200
160
12 Round
320
250
14 Round
480
375
16 Round
660
530
18 Round
880
680
20 Round
1200
900
CFM
Sheet metal or ductboard
Flexible duct (keep bends to minimum)