VI.
MISCELLANEOUS
Checks to make before pushing the Panic Button
SYMPTOM
CAUSE
Unable to calibrate one
Program module offset in socket
setpoint
or inverted.
High Alarm apparently
inoperative
'NEAR'setpoint set too close to
minimum range or within blanking
range.
(Turn near setpoint in
direction of arrow)
Erratic & Inability
to calibrate
'NEAR'and'FAR-setpoint controls
crossed (low set point placed
above the high setpoint)
Alarm settings unstable
when mode switch placed
in "run" position
Unable to calibrate
Low alarm
Time Delay excessive enabling
the level to enter the blanked
zone before alarming
Maximum range set to short
(Switch SW1)
6-l