![Milltronics Level Genie Instruction Manual Download Page 17](http://html1.mh-extra.com/html/milltronics/level-genie/level-genie_instruction-manual_1797006017.webp)
a delay in output response by 3 seconds or 10 seconds
depending on the position of the delay toggle.
I M P O R T A N T
Rotating the"NEAR"and"FAR"setpoints in the direction of
the arrows (on the PCB) brings the trip points closer
together.
Caution must be exercised not to cross these
controls.
The NEAR setpoint should always be set to a
higher level than the FAR setpoint.
USING ONLY ONE OF THE DUAL ALARMS
As a precaution,
to avoid having the NEAR and FAR settings
crossed, use only the FAR setpoint for single alarm operation.
Turn the NEAR setpoint fully counter clockwise.
HYSTERISIS
Approximately 0.5 in. (1.25cm) of hysterisis per foot of
range is provided.
Thus,
a high alarm 8 feet from the
transducer has a 4 inch deadband.
That is,
the material
would have to drop to 8.33 feet before the alarm would clear.