OM-244 023 Page 37
SECTION 7
−
OPERATING AUXILIARY EQUIPMENT
7-1. Auxiliary Power Receptacles
1
Circuit Breaker CB1
CB1 protects GFCI1 from overload. If a cir-
cuit breaker opens, the receptacle does not
work. Press CB1 to reset breaker.
2
Circuit Breaker CB2
CB2 protects GFCI1 from overload. If a cir-
cuit breaker opens, the receptacle does not
work. Press CB2 to reset breaker.
3
120V 15/20A AC Receptacles GFCI1,
GFCI2
Receptacles supply 60 Hz single-phase
power at weld/power speed.
If a ground fault is detected, receptacle Re-
set button pops out and receptacle does not
work. Check for faulty tools plugged into re-
ceptacle. Press button to reset receptacle.
At least once a month, run engine at
weld/power speed and press test but-
ton to verify GFCI is working properly.
Maximum output is 2.4 kVA/kW from each
GFCI and 4 kVa/kW from RC1.
Maximum combined output of all recep-
tacles is 4 kVA/kW.
EXAMPLE: If 13 A is drawn from RC1, only
7 A is available at GFCI1:
(240 V x 13 A) + (120 V x 7 A) =
4.0 kVA/kW
If a circuit breaker continues to open,
contact Factory Authorized Service
Agent.
4
Strain Relief Bushings
5
Ground Stud
4
2
3
1
238 127-A / 805 259-A