OM-2220 Page 13
50 Hz Models
Single
Phase
Three Phase
Input Voltage
230
230
380
400
415
Input Amperes At Rated Output
33
20
10
10
10
Max Recommended Standard Fuse Rating In Amperes
1
Time-Delay
2
40
20
10
10
10
Normal Operating 3
50
30
15
15
15
Min Input Conductor Size In AWG/Kcmil
10
14
14
14
14
Max Recommended Input Conductor Length In Feet (Meters)
88
(27)
69
(21)
188
(57)
208
(63)
224
(68)
Min Grounding Conductor Size In AWG/Kcmil
10
14
14
14
14
Reference: 1999 National Electrical Code (NEC)
1 Consult factory for circuit breaker applications.
2 “Time-Delay” fuses are UL class “RK5” .
3 “Normal Operating” (general purpose – no intentional delay) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” ( 65 amp and
above).
2-7.
Extension Cord Data
When calculating max. cord length, remember to include conductor length from
line disconnect device to input power receptacle.
NOTE
Input Voltage
Input Power
Phase
Hertz
Fuse Size Or
Circuit Breaker Rating
Conductor Size
Max. Cord Length
208 V
1
60
Time-Delay
2
45 A
Normal Operating
3
50 A
10 AWG
72 ft (22 m)
230 V
1
60
Time-Delay
2
40 A
Normal Operating
3
50 A
10 AWG
89 ft (27 m)
460 V
1
60
Time-Delay
2
20 A
Normal Operating
3
25 A
14 AWG
138 ft (42 m)
575 V
1
60
Time-Delay
2
15 A
Normal Operating
3
20 A
14 AWG
215 ft (66 m)
208 V
3
60
Time-Delay
2
25 A
Normal Operating
3
30 A
14 AWG
87 ft (27 m)
230 V
3
60
Time-Delay
2
20 A
Normal Operating
3
30 A
14 AWG
69 ft (21 m)
460 V
3
60
Time-Delay
2
10 A
Normal Operating
3
15 A
14 AWG
275 ft (84 m)
575 V
3
60
Time-Delay
2
10 A
Normal Operating
3
10 A
14 AWG
429 ft (131 m)
230 V
1
50
Time-Delay
2
40 A
Normal Operating
3
50 A
10 AWG
88 ft (27 m)
230 V
3
50
Time-Delay
2
20 A
Normal Operating
3
30 A
14 AWG
69 ft (21 m)
380 V
3
50
Time-Delay
2
10 A
Normal Operating
3
15 A
14 AWG
188 ft (57 m)
400 V
3
50
Time-Delay
2
10 A
Normal Operating
3
15 A
14 AWG
208 ft (63 m)
415 V
3
50
Time-Delay
2
10 A
Normal Operating
3
15 A
14 AWG
224 ft (68 m)
2 “Time-Delay” fuses are UL class “RK5” .
3 “Normal Operating” (general purpose – no intentional delay) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” ( 65 amp and
above).