10-8. Overload Protection (Deutz F3L912-Powered Units)
Ref. 802 313-A
2
1
9
8
7
4
Stop engine.
When a circuit breaker or fuse
opens, it usually indicates a more se-
rious problem exists. Contact Facto-
ry Authorized Service Agent.
1
Fuse F1
2
Fuse F2
F1 and F2 protect the stator exciter wind-
ing from overload. If F1 opens, weld and
generator power is low or stops entirely.
If F2 opens, weld output is low or stops
entirely. 4 kVA/kW generator power is still
available.
3
Circuit Breaker CB4 (Not Shown)
4
Circuit Breaker CB5
(CC/CV Models Only)
5
Circuit Breaker CB6
(CC/CV Models Only)
6
Circuit Breaker CB10 (Not Shown)
7
Circuit Breaker CB11
8
Circuit Breaker CB12
9
Circuit Breaker CB13
9
Circuit Breaker CB14
(Not Shown)
CB4 protects the welding arc drive (dig)
circuit. If CB4 opens, electrode may stick
to the workpiece more frequently during
low voltage (short arc length) conditions.
CB4 automatically resets when the fault
is corrected.
CB5 protects the 24 volt ac output to re-
mote receptacle RC14, and 24 volt output
to field current regulator board PC1 (CC/
CV models only). If CB5 opens, weld out-
put and 24 volt output to RC14 stops. On
units with optional three-phase genera-
tor, power output at receptacle RC5 also
stops if CB5 opens.
CB6 protects the 115 volt ac output to re-
mote receptacle RC14 (CC/CV models
only). If CB6 opens, 115 volt output to
RC14 stops.
CB10 protects the engine battery circuit.
If CB10 opens, the engine will not crank.
CB10 automatically resets when the fault
is corrected.
CB11 protects the engine wiring harness.
On CC models, if CB11 opens the max
OCV circuit does not work and open cir-
cuit voltage is variable at all times (see
max OCV note under Weld Controls in
Section 6-2). If CB11 opens on CC/CV
models, weld output stops (generator
power is still available).
CB12 protects the field flashing circuit. If
CB12 opens, the generator may not ex-
cite at start-up and weld and generator
power output may not be available.
CB13 protects the engine shutdown cir-
cuit. If CB13 opens, the engine cranks but
does not start.
CB14 protects the engine fuel solenoid.
If CB14 opens, the engine will not start.
CB14 automatically resets when the fault
is corrected.
Press button to reset breaker.
5
Summary of Contents for Big Blue 402D
Page 39: ...OM 495 Page 33 Return To Table Of Contents Notes...
Page 43: ...OM 495 Page 37 Return To Table Of Contents Notes...
Page 54: ...OM 495 Page 48 Return To Table Of Contents 9 2 Maintenance Label...
Page 62: ...OM 495 Page 56 Return To Table Of Contents 10 2 Maintenance Label...
Page 75: ...OM 495 Page 69 Return To Table Of Contents 215 302 A...
Page 77: ...OM 495 Page 71 Return To Table Of Contents 216 530 A...
Page 79: ...OM 495 Page 73 Return To Table Of Contents 215 303 A...
Page 81: ...OM 495 Page 75 Return To Table Of Contents 216 531 A...
Page 83: ...OM 495 Page 77 Return To Table Of Contents 215 298 A...
Page 85: ...OM 495 Page 79 Return To Table Of Contents 215 299 A...
Page 114: ......