16
6.3 Downlink Commands
EM310-UDL supports downlink commands to configure the device. Application port is 85 by
default.
Example:
Set reporting interval as 20 minutes.
-END-
Channel
Type
Value
04
00 (Device
Position)
00=Normal
Channel
Type
Description
ff
03 (Set Reporting Interval)
2 Bytes, unit: s
ff03b004
Channel
Type
Value
ff
03 (Set Reporting
Interval)
b0 04 => 04 b0 = 1200s
= 20 minutes