25
FAULT FINDING
Chart 4
Check fan/flue gas system
Does fun run ?
YES
Is air pressure
switch activated ?
YES
Go to chart 5
NO
Differantial air
pressure across
the air pressure
switch is greater
than 48 Pascal ?
YES
Check and if
necessary
replace air
pressure switch
NO
Check and clean fan
Check flue and air intake are
correct and clean
Check air pressure switch tube is
clean
NO
Is 230 Vac present
across fan terminals ?
NO
Check air pressure switch
wiring connection
YES
Check and if necessary
replace fan
Check and if necessary
replace ignition board
Chart 5
Check D.H.W. and C.H. modulation
Boiler operated on
central heating mode
Boiler operated on
DHW mode
Does burner flame
modulate ?
Check wiring connection
to CH sensor
NO
YES
Normal operation
carry out
Does burner flame
modulate ?
YES
Normal operation
carry out
Check wiring connection
to DHW sensor
NO
Check DHW sensor and main control
board and replace them if necessary
Check CH sensor and main control board
and replace them if necessary
Check modulating coil and replace it if necessary
Check modulating coil and replace it if necessary