RECORDS

a.

Record the 3 latest tripped faults current or “tSt” for manual trip test.

b.

The records are stored in non-volatile memory.

c.

To clear the entire record database:

Step 1: When the relay is healthy, press [RESET] button to step to most recent trip fault record or [FUNC] digit 
shown “A”.

Step 2: Press [

] and [

] buttons simultaneously and hold for 3.5s or the [DATA] show “0”. It will clear the 

entire fault records database.

10.

TECHNICAL DATA

AUXILIARY SUPPLY

RECORDS

MK330A-230A........................184~276 VAC

Fault record....................... 3 latest trip fault current or “tSt”

MK330A-110A........................94~127 VAC

for manual trip test

Rated frequency.....................50Hz or 60Hz 

Storage.............................. Non-volatile memory

VA Rating...............................3 VA typical

SETTING RANGES

DIGITAL INPUT PORT

Sensitivity adjustment............ 30mA, 50mA, 

Remote reset..................... N.O. Dry contact

0.10~1.00A (step=50mA), 
1.00~10.0A (step=1.00A)

OUTPUT CONTACTS

Delay time adjustment........... Instantaneous, 

Contact rating.................... 5A (NO) / 3A (NC) / AC1

0.1~3.0s (step=0.1s) 

Contact arrangement......... Change over

Number of shots.....................0~30 (step=1)

Expected electrical life.......10,000 at rated current

0=Disable reclose function

Expected mechanical life...5,000,000 operations

Dead time...............................1~500sec (step=1sec)
Persistent fault time............... 0~500sec (step=1sec)

ZERO-PHASE CURRENT TRANSFORMERS

0=Disable

To operate with Mikro's ZCT series of current transformers

Reclaim time.......................... 0~500min (step-1min)

0=Disable

MECHANICAL

Lockout self reset time........... 0~200hrs (step=1hour)

Mounting............................Standard DIN 96x96mm panel 

0=Disable

mounting

Programmable contact...........0~6 (step=1)

Approximate weight........... 0.58kg (excluding ZCT)

INDICATORS

Pre-fault alarm....................... Red indicator
Leakage trip delay time..........Red indicator
Leakage trip........................... 7-segment display and red indicators
Manual test trip...................... 7-segment display and red indicators
ZCT connection fault..............7-segment display and red indicators
Trip records............................7-segment display
Real-time leakage current......7-segment display

11.

CONNECTION DIAGRAM

12.

CASE DIMENSION

MK330A Self-Reclosing Earth Leakage Relay
User's Manual

A BRIEF OVERVIEW

1.

DESCRIPTION

The MK330A is microprocessors based earth leakage relay with built in self-reclosing function. 

The earth leakage protection module is designed for measure the low-level current flowing from the live 
part of the installation to the earth in the absent of the insulation fault. A zero phase current transformer 
is connected to the relay and function as the sensor for sensing the leakage current. All conductors of 
the circuit to be protected shall go through the ZCT.

While the  self reclosing  module  provide  multiple number  of shots  operation.  It  also  incorporates 
intelligent to differentiate the transient fault or persistent fault.

Symbols

I     

 -  Sensitivity setting

SHOTS   -  Nos of reclose operations

n

tDEAD 

 -  Dead time

tPF           -  Persistent fault monitoring time

a  -  DATA display

b  -  Trip status indicator

c  -  Alarm status indicator

d  -  DP2 indicator

e  -  Decrement button

f   -  Increment button

g  -  RESET button

h  -  TEST button

i   -  Model

j   -  DP1 indicator

k  -  FUNC display

a

g

c

d

e

i

j

k

b

f

h

tLAR         -  Lockout auto reset time

tREC        -  Reclaim time

RLY2        -  Programmable Output contact 

   

 -  Time time delay setting

    Flt 1          -  Fault record #1(Most recent)

    Flt 2          -  Fault record #2

    Flt 3          -  Fault record #3(Oldest)

   t    

90mm
70mm

96mm

96mm

SIDE

FRONT

  PANEL
CUTOUT

91±0.5mm

91±0.5mm

TRIP SAFE
CONTACT*

6

2

3

4

5

7

1

9

11

12

13

14

15

L

N

AUX

8

16

10

        ALARM 
      CONTACT

LOAD

COM

The EARTH wire 
must not pass
through the ZCT

L1  L2  L3  N                             PE

MK330A

REMOTE
  RESET

CONTACTOR

MIKRO
ZCT

NO

NC

COM

NO

NC