2. LIGHT INDICATORS

[Trip]

LED

[Alarm]

LED

[FUNC]

display

[DP1]

indicator

[DATA]

display

Status

0

0

0

0

0

No auxiliary supply

0

0

X

X

1

Normal condition, no tripping

0

B

X

X

X

Leakage current > 50% of the I

n

0

FB

X

X

X

Leakage current > 85% of the I

n. Trip time delay 

running.

1

1

0

0

B

Relay tripped

0

0

1

0

1

Scroll through setting

0

0

1

1

1

Scroll through records

0

0

B

0

1

[DATA] programming mode

1

1

X

X

“Ct”

ZCT connection fault

X

X

X

X

“tSt”

Manual trip test

Table 1: Relay status displayed

1 = ON

0   = OFF

X = Don't care

B = Normal blink

FB = Fast blink

3. PUSH BUTTONS OERATION

a.

Integral Trip Test:

Press the [TEST] button and hold for 3.5s to perform an integral test on the relay ranging from the 

analog sensing circuitry to output contact(s) of the relay as well as the relay indicators and display.

During the testing process, the first 2s is to simulate the pre-fault alarm condition then follow by 1.5s 

testing on the trip time delay. End of  time delay, relay trip.

b.

Leakage Fault Trip Reset: / Manual Test Trip Reset:

Press the [RESET] button once or through digital input port.

c.

ZCT Connection Fault Reset: 

Press the [RESET] button once or through digital input port. 

Reset is inhabited if the fault is not rectify.

d.

Parameters Viewing:

When the relay is operate normal and healthy condition, press the [RESET] button to step through 

the various functions.

When step through the parameters, press [RESET] button and hold for 1.5 second to jump direct to 

the default [FUNC].

[FUNC] [DP1]

[DP2]

Symbols

Description

Blank

Off

Note 1

Real-time leakage current display (Default)

1

Off

X

I

n

Sensitivity setting (A)

2

Off

X

t

Trip time delay setting (second)

A

On

Note 1

Flt 1

Fault record #1 (Most recent)

b

On

Note 1

Flt 2

Fault record #2

c

On

Note 1

Flt 3

Fault record #3 (Oldest)

Table 2: List of [FUNC] code displayed

Note 1: 

If DP2 is OFF. The unit for the [DATA] displayed is in mA.

If DP2 is ON. The unit for the [DATA] displayed is in ampere (A).

e.

Parameters Setting

Step 1: Press [RESET] button to step to desired [FUNC] or parameter.

Step 2: Press [ ] and [ ] buttons simultaneously and hold for 1.5s to enter programming mode. 

The [FUNC] digit blink to indicates the relay has enter into the programming mode.

Step 3: Press [ ] or [ ] button to increase or decrease the parameter value.

Step 4: To save the selected value, press [ ] and [ ] buttons simultaneously and hold for 1.5s. It 

will exit the programming mode with [DATA] displaying the new setting.

To exit programming mode without saving the selected setting, press the [RESET] button once.

4. DIGITAL INPUT PORT *

a.

These digital port is for remotely reset the relay when tripped or ZCT connection fault.

b.

To reset the relay, make a connection between terminals 4 and 5 of the relay.

5. OUTPUT CONTACTS

Trip  Contact

Activated and latch by leakage fault trip, manual test trip or ZCT connection fault

Positive Safety 

Contact *

Activated when the relay is power up and function correctly with no tripping.

Pre-fault Alarm 

Contact *

Activated when the measured leakage current > 50% of the I

n and self reset when the 

measured leakage current < 45% of the I

n. 

Activated and latch when the relay is tripped.

Table 3: Output contact description

6. RECORDS

a.

Record the 3 latest tripped faults current or “tSt” for manual trip test.

b.

The records are stored in non-volatile memory.

c.

To clear the entire record database:

Step 1: When the relay is healthy, press [RESET] button to step to most recent trip fault record or 

[FUNC] digit shown “A”.

Step 2: Press [ ] and [ ] buttons simultaneously and hold for 3.5s or the [DATA] show “0”. It will 

clear the entire fault records database.

7. TECHNICAL DATA

AUXILIARY SUPPLY

MK300A-230(6) / MK300EA-230(6)............................... 184~276 VAC

MK300A-110(6) / MK300EA-110(6)............................... 94~127 VAC

Rated frequency............................................................. 50Hz or 60Hz

VA rating.........................................................................3 VA typical

SETTING RANGES

Sensitivity adjustment.....................................................30mA, 50mA, 

0.10~1.00A (step=50mA),

1.00~10.0A (step=1.00A)

Delay time adjustment.................................................... Instantaneous, 

0.1~3.0s (step=0.1s)

RECORD

Fault record.................................................................... 3 latest trip fault current or “tSt” for manual trip test

Storage........................................................................... Non-volatile memory

DIGITAL INPUT PORT

Remote reset.................................................................. N.O. Dry contact

OUTPUT CONTACTS

Contact rating................................................................. 5A(NO) / 3A(NC) / 250V AC1

Contact arrangement......................................................Change over

Expected electrical life....................................................10,000 at rated current

Expected mechanical life................................................5,000,000 operations

MK300A-240AD(6) / MK300EA-240AD(6)..................... 85~265VAC/110~340VDC