SPECIFICATIONS

INPUT RANGE

Select any input range within the
following limits

Voltage

Min span 1 V, Max input 250 V

Offset 0 V min, +100% of span max
(example, +10/+20 V)

For negative offsets, use MM1000

Current

Min span 1 mA, Max input 100 mA

Offset 0 mA min, 100% of span max
(example, +50/+100 mA)

For negative offsets, use MM1000.

INPUT IMPEDANCE

Voltage    200 kilohms
Current    see table in block diagram

SETPOINT

0 to 100% of span, min.

DEADBAND

1% to 100 % of span, min.

RESPONSE TIME

20 ms typical

ACCURACY

±0.1% of span

COMMON MODE REJECTION

120 dB, DC to 60 Hz

RELAY CONTACTS

(dpdt)

Resistive Load:

5 A max, 150 W max, 220 VAC max,
30 VDC max

Inductive Load:
(Power factor ³ 0.4):

2.5 A max, 75 W max, 220 VAC max,
30 VDC max

OPERATING TEMPERATURE

14°F to 140°F/-10°C to 60°C

TEMPERATURE STABILITY

±0.02% of span/°C max

POWER  

(2.5 W max)

115 VAC ±10%, 50 or 60 Hz
230 VAC ±10%, 50 or 60 Hz

(DC Power Option)

12 VDC (limits 10 VDC to 15 VDC)
24 VDC (limits 21 VDC to 32 VDC)

Isolation, DC power supply

to input common: 10 megohms

MOUNTING

The module is designed to plug into a stan-
dard 11-pin relay socket.  (MP011) is a
molded plastic socket suitable for mounting
on a flat surface or snap into a 2 3/4 inch wide
PVC track (TRK48).

A hold-down clip (CLP1) is available for
installation where vibration may be a prob-
lem.

A DIN rail mounted socket (DMP011) is avail-
able for 35mm symmetrical DIN rail.

A Killark HK Series explosion-proof housing
with dome and 11 pin socket is available
(HKB-HK2D-11).

WARRANTY

The Mighty Module Series of products carry
a limited warranty of 10 + 5 years. In the
event of a failure due to defective material
or workmanship, during the 10 year period,
the unit will be repaired or replaced at no
charge. For a period of 5 years after the
initial 10 year warranty, the unit will be
repaired, if possible, for a cost of 10 % of
the original purchase price.

Relays are not covered by the warranty.

Specifications are subject to change without notice.  © 2007 Wilkerson Instrument Co., Inc.                 DWG#W102454  3/07