Installation

*INSTALLATION*

Non-return flap

Use a non-return flap in the exhaust
system.

A non-return flap ensures that when the
cooker hood is not in operation, the
duct is closed to prevent unwanted
exchange of room air and outside air.

If the exhaust is ducted through an
outside wall, a Miele wall vent or roof
vent (available as an optional
accessory) is recommended. Both of
these have a built-in non-return flap.

If the on-site ventilation system does
not have a non-return flap, one is
supplied with the cooker hood.

The non-return flap is fitted in the
exhaust socket of the fan.

Condensation

If the exhaust ducting is to run through
cool rooms or ceiling space, for
example, the significant variations in
temperature between the different areas
can cause condensation to form.
Insulate the exhaust ducting to reduce
temperature variations.

If the exhaust ducting is to be laid
horizontally, it must be laid with a
downwards sloping gradient of at least
1 cm per meter. This is to ensure that
condensation cannot drain back into
the cooker hood.

In addition to insulating the exhaust
ducting, it is advisable to also install a
condensate trap for collecting and
evaporating any potential condensation.

Condensate traps for 125 mm or
150 mm diameter exhaust ducting are
available as optional accessories.

When installing a condensate trap,
ensure that it is positioned vertically
and as closely as possible to the cooker
hood above the exhaust connection.
The arrow on the casing indicates the
direction of airflow.

Miele shall not accept warranty claims
for any functional defects or damage
caused by inadequate exhaust
ducting.

Summary of Contents for DAS 4620

Page 1: ...y to dismantle in the event that service is required This should be taken into consideration when planning the position of cupboards shelves ceilings or features in the vicinity of the cooker hood Installation materials 1 vent connection for exhaust ducting 150 mm 1 non return flap for fitting into the exhaust socket on the motor unit not needed for recirculation mode Depending on the model the no...

Page 2: ...1839970 DML 2000 installation kit for installing a hinged front panel to match kitchen furniture units not supplied available as an optional accessory Installation materials for recirculation mode You need the following optional accessories for recirculation mode DFKS 31 x installation kit contains 2 holders and 2 charcoal filters DFKS 31 P with single use charcoal filters or DFKS 31 R with reacti...

Page 3: ...12062340 01 Installation INSTALLATION Appliance dimensions Dia 1 DAS 4620 in a 600 mm wide cabinet The drawing is not to scale ...

Page 4: ...12062340 01 Installation INSTALLATION Dia 2 DAS 4920 in a 900 mm wide cabinet The drawing is not to scale See diagram 1 for side view ...

Page 5: ...e cabinet it must be removable c Extraction or recirculation with conversion kit DUU 150 d DML 2000 bracket optional accessory for fitting a front panel In this installation situation the deflector plate is flush with the front edge of the housing unit carcase If you wish to position the cooker hood further forward or further back you must adapt the dimensions accordingly e g if you are using a fr...

Page 6: ...Electric hob 450 mm Electric grill deep fat fryer electric 650 mm Multi burner gas hob total output 12 6 kW no burner 4 5 kW 650 mm Multi burner gas hob total output 12 6 kW and 21 6 kW no burner 4 8 kW 760 mm Multi burner gas hob total output 21 6 kW or multi burner gas hob where one burner 4 8 kW Not possible Single burner gas hob output 6 kW 650 mm Single burner gas hob output 6 kW and 8 1 kW 7...

Page 7: ... the lowest noise levels please note the following The diameter of the exhaust ducting must not be smaller than the cross section of the exhaust duct see Appliance dimensions This applies in particular when using flat ducting The exhaust ducting should be as short and straight as possible Only use wide radius bends The exhaust ducting must not be kinked or compressed All connections must be strong...

Page 8: ...n temperature between the different areas can cause condensation to form Insulate the exhaust ducting to reduce temperature variations If the exhaust ducting is to be laid horizontally it must be laid with a downwards sloping gradient of at least 1 cm per meter This is to ensure that condensation cannot drain back into the cooker hood In addition to insulating the exhaust ducting it is advisable t...

Page 9: ...ot only reduces noise from the fan outside the house but also sounds originating outside reaching the kitchen through the exhaust ducting e g traffic noise For this reason the silencer must be positioned as close as possible to the ducting exit In recirculation mode the silencer needs to be positioned between the exhaust vent and the exhaust grille Check that there is sufficient space ...

Page 10: ...he Miele Customer Service Department For safety reasons such replacement may only be carried out by a qualified specialist or the Miele Customer Service Department These operating instructions and the data plate indicate the nominal power consumption and the appropriate fuse rating Compare this information with the data of the on site electrical connection If in any doubt consult a qualified elect...

Reviews: