MidNite Classic 150-SL Owner'S Manual Download Page 30

Classic SL owner’s manual REV E 2056 

 
 
 

30 | 

P a g e                                                                                                                       1 0 - 0 0 1 - 3       R E V :   E

 

 

 
 

 
Classic goes to Float to 
early 

*Make sure End Amps is not set to high causing the Classic to go to Float (End 
Amps is in the Charge menu and the way it works is if the charge current falls 
below the End Amps setting AND the Classic is in Absorb the Classic will go 
to Float. Setting End Amps to 0 will disable it. End Amps setting is a value the 
battery manufacturer supplies 
*Make sure you have the Absorb time is set properly 

Follow Me with my 
Classic Lite is not 
working 

*Classic Lites older than serial # CL05435 did not work with Follow Me 
please call customer service for a new MNLP 
*Verify you are seeing the short blips of the blue LED internally as talked 
about above. If not please check all your cables. 

My Classic says “OCP is 
OFF” on the display 

*This can happen on older Classics that have had the firmware updated. This 
will have no effect on the operation of the classic but to make the message go 
away do a factory restore to fix this. (Warning all settings will be lost) 

My Classic says “OCP” 
now and then on the 
display 

*This can be normal if the battery bank is small or the inverter cables are too 
small. If this shows up just once in a great while that would be ok but if it is 
happening pretty regularly you may want to look at the size of the battery 
cables, Age of the battery bank or the size of the battery.  Call customer service 
for assistance 

My Classic has an 
orange LED on the 
display lit up and or says 
“Amp Limit” 

*This indicates the Classic is current limiting. Either because it has reached the 
current limit you have set in the Charge menu under limits or because it is to 
hot and it is backing its current down to prevent overheating. Go into the Main 
menu and the Charge category, Look in the Limits sub menu and verify the 
amp limits for In and Out are set to what you desire. 

My Classic says “Hyper 
VOC’ on the display 

*This is indicating that the input voltage has exceeded the operational voltage 
of the Classic. If this is happening now and then on rare occasions when it is 
really cold then this is normal. If this is happening all the time this indicates 
the PV array was wired for too high a voltage, Please consult your installer for 
assistance with that 

My Classic says 
“Battery over V” on the 
display 

*This is an indication the Classic thinks the battery voltage is to high and has 
stopped charging. 
*This can happen with multiple controllers that are not networked together if 
one of the classics goes to float it can show this and will go away as soon as 
the other controller goes to float. 
*If this is a new install the wrong nominal voltage may be selected and a 
factory restore will be needed. 
*if this is a running system then you may have another charging source that 
has malfunctioned and over charging the battery bank 

My Classic says “GRND 
FLT” on the display and 
is making a loud 
beeping 

*Generally this would be caused by the PV or Battery positive shorting to 
ground somewhere in the system. The first thing to do is verify it is a real fault 
by carefully measuring between Battery Negative and Earth ground. If you see 
any voltage here than the system has a fault. Call your installer for help finding 
and rectifying the fault. The Classic will automatically stop showing the fault 
when the issue is fixed 

 
 

Summary of Contents for Classic 150-SL

Page 1: ...e Classic will not survive MidNite does not recommend the use of Tigo Module Optimizers with the Classic If Tigo modules must be installed Legacy P O MUST be used When the Classic is used with Wind or...

Page 2: ...erters or charge controllers can occur Take a single XW E Panel for example it has a positive bus bar for Charge controller battery side connections This bus bar is sufficient for 2 charge controllers...

Page 3: ...Classic SL owner s manual REV E 2056 3 P a g e 1 0 0 0 1 3 R E V E This Manual covers models Classic 150 SL 200 SL 250 SL...

Page 4: ...to the accuracy sufficiency or suitability of any technical or other information provided in its manuals or other documentation b Assumes no responsibility or liability for loss or damage whether dire...

Page 5: ...Mechanical 36 Classic Breaker sizing 37 Scope This Manual provides safety guidelines and installation information for the Classic SL charge controller It does not provide brand specific information a...

Page 6: ...ctions must be kept separate from the grounding conductor connections The equipment ground terminal inside the Classic must be connected to Earth Ground for the internal DC GFP to work With the except...

Page 7: ...ttery manufacturer for details WARNING PERSONAL PRECAUTIONS DURING INSTALLATION WARNING BATTERIES PRESENT RISK OF ELECTRICAL SHOCK BURN FROM HIGH SHORT CIRCUIT CURRENT FIRE OR EXPLOSION FROM VENTED GA...

Page 8: ...Classic SL owner s manual REV E 2056 8 P a g e 1 0 0 0 1 3 R E V E Classic SL Power Graphs Sizing the Solar Array Table 1 Table 2 Table 3...

Page 9: ...ller needs to have the open circuit voltage of the array about 30 higher than the highest battery voltage you plan to charge to NOTE You can find the Classic string sizing tool on the web page www mid...

Page 10: ...screened Parts bag with stickers Terminal block cover and silicone grease User s manual printed Email customerservice midnitesolar com for more information or if anything is missing or damaged Figure...

Page 11: ...cover in place See Figure 2 Do not force the cover if it does not seat into place easily stop and look for any cables or wires that may be interfering With the cover seated in place install the four...

Page 12: ...and 2 plastic bushings are included with each E Panel One locknut acts as a spacer Carefully hang the Classic on the screw in the bracket and slide it over the close nipple see figure 4 Install the l...

Page 13: ...ng the Classic front cover ALWAYS use proper Over current devices and disconnects on the PV and Battery at the Classic MidNite DC breakers work well for both WARNING to comply with Australian New Zeal...

Page 14: ...on the DC terminal connector big blue terminal connector are Up to 10 AWG torque to 25 35 inch pounds 8 AWG torque to 30 40 inch pounds 6 AWG or above Torque to 40 50 inch pounds HyperVOC HyperVOC is...

Page 15: ...battery cable to this bus bar 22 Earth Ground Bus Bar This is the common Earth Ground bus bar where all the grounds get wired back to and it needs to be connected to the building s ground rod system 2...

Page 16: ...Classic SL owner s manual REV E 2056 16 P a g e 1 0 0 0 1 3 R E V E Diagram 1...

Page 17: ...he parts bag Maximum and Minimum Wire Size The Classic s Blue DC terminal connector will accept wire from 14 4 AWG The Classic s Aux 1 and 2 terminal connector will accept wire up to 18 AWG WARNING Ex...

Page 18: ...late rating in extreme situations so the safe minimum wire size should be selected for the PV array maximum short circuit current Please consult PV manufacturer for specifications The US National Elec...

Page 19: ...k of injury charge only properly rated such as 6 V 12 V and 24 V lead acid GEL AGM Flooded or Nickel Cadmium rechargeable batteries Other battery types may burst causing personal injury and damage WAR...

Page 20: ...Classic SL owner s manual REV E 2056 20 P a g e 1 0 0 0 1 3 R E V E Figure 8 Insert BTS to the jack labeled BATTERY TEMP on the control board Figure 9...

Page 21: ...ical connection compartment Figure 10 DC System Grounding The Classic charge controller is designed to work with Negative Ground Positive Ground or Ungrounded power systems In grounded systems dc nega...

Page 22: ...12 The Ground fault device is simple to understand and use It detects a fault between battery PV negative and earth ground just like the breaker DC GFP system The difference with the Classic is that i...

Page 23: ...e the Quick Set Equalization To do a manual Equalization charge go into the Charge menu and highlight EQ and press Enter Now EQ Stopped will be highlighted Scroll up to select Eq Started Press the Sta...

Page 24: ...the bottom right corner of the display then the Mode may have been turned off To turn the mode back ON push the Main Menu button several times until Charge is highlighted Scroll to the right until Mo...

Page 25: ...he Enter Button Press the right arrow key to highlight the Out Amps column Use the up and down arrow keys to change the current limit then press the Enter Button to save this data Calibrating Battery...

Page 26: ...if the power source goes off It has two settings that are user adjustable Sweep Interval is the time between mini sweeps in minutes and sweeps around the present i e the last found MPP Voltage The ran...

Page 27: ...LL settings Turn the PV breaker and Battery breaker off What you don t have a breaker Get one asap and make sure the display has gone dark Do a hardware factory restore There are 4 sets of jumpers dir...

Page 28: ...the PV positive and negative on the blue terminal block inside the Classic If the system has been running all along and this just happened call customer service The Display is showing all 0s and or G...

Page 29: ...e Classic up Count to 4 before turning the breaker on If you do not have a breaker or disconnect and you are trying to connect a wire to a terminal block or a battery the connection will likely be to...

Page 30: ...because it has reached the current limit you have set in the Charge menu under limits or because it is to hot and it is backing its current down to prevent overheating Go into the Main menu and the C...

Page 31: ...en or I don t see all the settings shown in the manual If the WBjr status menu is not present or does not match the manual then you most likely have older firmware We recommend updating the firmware a...

Page 32: ...c Lite powered on Now you can change the network settings on the Local App if you want Note setting switches to custom first and then powering the Classic Lite can cause issues trying to connect as it...

Page 33: ...ll 6 pins inside the jack Carefully so as not to bend the pins the fans should all start spinning How do I find the Wizard You won t we removed the wizard as it asked a lot of questions that did nothi...

Page 34: ...o the right of this it will say the battery voltage it is programmed to Example 48v I have Aux1 programmed properly but I cannot get 12v out of it when I should Most likely the Jumpers on the bottom l...

Page 35: ...t 24v battery 65a at 48v battery 60a at 12v battery 62a at 24v battery 55a at 48v battery De rate current at 40 C 80 amperes 66 amperes 52 amperes Environment 40c to 40c Dimensions of Classic 14 87 X...

Page 36: ...Classic SL owner s manual REV E 2056 36 P a g e 1 0 0 0 1 3 R E V E Specifications Mechanical Figure 13...

Page 37: ...Classic SL owner s manual REV E 2056 37 P a g e 1 0 0 0 1 3 R E V E Classic Breaker sizing Table 7...

Page 38: ...Classic SL owner s manual REV E 2056 38 P a g e 1 0 0 0 1 3 R E V E...

Page 39: ...Classic SL owner s manual REV E 2056 39 P a g e 1 0 0 0 1 3 R E V E...

Page 40: ...Classic SL owner s manual REV E 2056 40 P a g e 1 0 0 0 1 3 R E V E...

Page 41: ...Classic SL owner s manual REV E 2056 41 P a g e 1 0 0 0 1 3 R E V E Table 8...

Page 42: ...Float Constant voltage charge stage with a lower voltage than the Absorb charge point The controller is regulating so maximum power will not be seen at this time Float MPPT Maximum current charge sta...

Page 43: ...erature sensor to measure the ambient temperature of the battery bank and will adjust the voltage set points up or down accordingly to ensure a full battery There are 3 parameters to set Minimum and M...

Reviews: