MNDC-GFP100 Instructions (continued) 

 

2 | 

P a g e                                                                                                                       1 0 - 2 2 3 - 1         R E V :   -

 

 

 

 

The MNDC-GFP100 Ground Fault Protector is a 4 position panel mount breaker that disconnects power in the 
event of a ground fault. The MNDG-GFP100 mounts easily in an E-Panel or other similar electrical box. 
 
The MNDC-GFP100 can be wired to sense the ground fault directly or to be remotely tripped. The Classic 
Charge Controller can sense faults and send a signal to the MNDC-GFP100 to cause it to open the protected 
circuits.  See wiring diagrams starting on the next page. 

When installing a DC-GFP in the PV circuit, make sure there is no battery minus to ground connection. That 
would effectively short out the sense circuit on the DC-GFP. 
MidNite solar offers other  DC-GFP devices. One is a 63 amp single circuit din rail mount device another is an 
80 amp single circuit panel mount device. There is also a 50 amp 300VDC device.  
 
The Midnite Dual GFP-100 is ideal for dual arrays. DC-GFP’s are a very misunderstood device. When looking 
at a wiring diagram you will notice that part of the DC-GFP is a high current breaker. Connected in series with 
the GFP is yet another high current DC breaker. It is a common mistake to think the second breaker is 
unnecessary. 
 

NEC2008 requires a DC-GFP on all systems

 whether mounted on the roof top of a residence or not. The NEC 

also does not allow the DC-GFP to be the PV disconnect. When the DC-GFP is turned off, it leaves the battery 
negative ungrounded. The only time it is allowed that the system be ungrounded is during a fault condition. 
This requirement necessitates a PV disconnect in series with the DC-GFP.  Some DC-GFP’s such as the 
Midnite Solar MNDC-GFP100-Dual breaker break both the positive and negative circuits, this provides the 
highest level of protection. 
 
If tripping occurs, check wiring carefully. More often than not, there is a wiring error. 
 

Important! 

Torque connections to 30 In-Lbs (3.4NM)  

Breaker Identification Label. This view is from the back of the breaker (near the connection studs). 
The breaker is silkscreened P1 through P4 on the top of the breaker near the connections. 
 
Note: 
For Battery-less DC-GFP installations connect the white wire to PV negative rather than Battery negative. 

Summary of Contents for DC-GFP 100

Page 1: ...current independent of ambient temperature The MNDC GFP100 can be used in the following ways 1 pv array breaking pv and using the 1 amp pole as the trip source 1 pv array breaking pv and using the classic to shunt trip the device 2 pv arrays breaking just the using the 1 amp pole as a trip source 2 pv arrays breaking just the using the classic to shunt trip the device MIDNITE SOLAR INC 17722 67TH ...

Page 2: ...wiring diagram you will notice that part of the DC GFP is a high current breaker Connected in series with the GFP is yet another high current DC breaker It is a common mistake to think the second breaker is unnecessary NEC2008 requires a DC GFP on all systems whether mounted on the roof top of a residence or not The NEC also does not allow the DC GFP to be the PV disconnect When the DC GFP is turn...

Page 3: ...EAKER MNDC GFP 100 SINGLE ARRAY POSITIVE AND NEGATIVE P V LINES DISCONNECTED UPON 1 AMP GROUND FAULT BATT NEG T CARPENTER 3 5 13 1 0 0 1 ON 100 80 ON 100 SHUNT TRIP GROUND BATTERY NEGATIVE PV ARRAY CLASSIC MPPT CHARGE CONTROLLER MNDC GFP 100 PV POS PV NEG PV POS PV INPUT BREAKER MNDC GFP 100 SINGLE ARRAY POSITIVE AND NEGATIVE P V LINES DISCONNECTED BY CLASIC S BUILT IN GFP BATT NEG AUX 1 T CARPENT...

Page 4: ...NEG MNDC GFP 100 TWO ARRAYS TWO CONTROLLERS P V POSITIVE DISCONNECT ONLY SELF TRIPPING ON 1 AMP GROUND FAULT T CARPENTER 3 5 13 1 0 0 1 ON 100 80 ON 100 SHUNT TRIP GROUND BATTERY NEGATIVE PV ARRAY CLASSIC MPPT CHARGE CONTROLLER MNDC GFP 100 AUX 1 PV POS PV NEG PV POS PV INPUT BREAKER PV POS PV NEG CLASSIC MPPT CHARGE CONTROLLER PV POS PV INPUT BREAKER BATT NEG BATT NEG MNDC GFP 100 TWO ARRAYS TWO ...

Reviews: