Braze the liquid line to the high pressure valve (liquid valve) at the outdoor unit. Be sure to wrap
the valve body with a wet rag. Allow the nitrogen to continue flowing.
Carefully remove the rubber plugs from the evaporator liquid and vapor connections at the
indoor unit.
Braze the liquid line to the indoor liquid connection. Nitrogen should be flowing through the
evaporator coil.
Slide the plastic cap away from the vapor connection at the indoor coil. Braze the vapor line to
the evaporator vapor connection.
Protect the vapor valve with a wet rag and braze the vapor line connection to the outdoor unit.
The nitrogen flow should be exiting the system from the vapor service port connection. After this
connection has cooled, remove the nitrogen source from the liquid fitting service port.
Replace the Schrader core in the liquid and vapor valves.
Leak test all refrigerant piping connections including the service port flare caps to be sure they
are leak tight.
Do not over tighten. (between 40 and 60 inch-lbs. maximum)
Evacuate the vapor line, evaporator and the liquid line, to 500 microns or less.
Replace cap on service ports. Do not remove the flare caps from the service ports except when
necessary for servicing the system.
Do not connect manifold gauges unless trouble is suspected. Approximately 3/4 ounce of
refrigerant will be lost each time a standard manifold gauge is connected.
Release the refrigerant charge into the system. Open both the liquid and vapor valves by
removing the plunger cap and with a hex wrench back out counter-clockwise until valve stem
Summary of Contents for TempMaker Series
Page 29: ...MCAC UTSM 2014 03 R410A 380 415V 3Ph 50Hz TempMaker Series Split AC 28 MHA 150HWN1 MHA 192HWN1...
Page 39: ...MCAC UTSM 2014 03 R410A 380 415V 3Ph 50Hz TempMaker Series Split AC 38 MHA 150HWN1 MHA 192HWN1...
Page 45: ...MCAC UTSM 2014 03 R410A 380 415V 3Ph 50Hz TempMaker Series Split AC 44 3 Dimensions Unit mm...
Page 47: ...MCAC UTSM 2014 03 R410A 380 415V 3Ph 50Hz TempMaker Series Split AC 46 5 Refrigerant circuits...
Page 48: ...R410A 380 415V 3Ph 50Hz TempMaker Series Split AC MCAC UTSM 2014 03 47 6 Wiring Diagrams...
Page 59: ...MCAC UTSM 2014 03 R410A 380 415V 3Ph 50Hz TempMaker Series Split AC 58 MOV 120HN1 R Top view...
Page 63: ...MCAC UTSM 2014 03 R410A 380 415V 3Ph 50Hz TempMaker Series Split AC 62 MOV 150HN1 R...
Page 64: ...R410A 380 415V 3Ph 50Hz TempMaker Series Split AC MCAC UTSM 2014 03 63 MOV 192HN1 R...
Page 94: ...R410A 380 415V 3Ph 50Hz TempMaker Series Split AC MCAC UTSM 2014 03 93 Floor standing type...
Page 150: ...R410A 380 415V 3Ph 50Hz TempMaker Series Split AC MCAC UTSM 2014 03 149 3 The wire connection...