background image

Midea R410A Direct Heating Commercial Heat Pump 50Hz Technical Manual          MCAC-HTSM-201506 

 

 
 

Midea R410A 

Direct Heating Commercial Heat Pump 

50Hz 

Technical Manual 

 
 
 
 
 
 

Applicable Model:     
 

                                  RSJ-420/SZN1-H 

                                  RSJ-800/SZN1-H 

 

 

 

 

Midea reserves the right to discontinue, or change specification or designs at any time without notices and 
without incurring obligations. 

 

Summary of Contents for RSJ-420/PZN1-H

Page 1: ...CAC HTSM 201506 1 Midea R410A Direct Heating Commercial Heat Pump 50Hz Technical Manual Applicable Model RSJ 420 SZN1 H RSJ 800 SZN1 H Midea reserves the right to discontinue or change specification o...

Page 2: ...MCAC HTSM 201506 Midea R410A Direct Heating Commercial Heat Pump 50Hz Technical Manual 2 Content Part 1 General information 3 Part 2 Performance 5 Part 3 Installation 26 Part 4 Controller 62...

Page 3: ...Midea R410A Direct Heating Commercial Heat Pump 50Hz Technical Manual MCAC HTSM 201506 3 Part 1 General information 1 Model Names of Units 4 2 External Appearance 4 3 Nomenclature 4...

Page 4: ...ect heating Type RSJ 420 SZN1 H 380 415V 3Ph 50Hz RSJ 800 SZN1 H 380 415V 3Ph 50Hz 2 External Appearance RSJ 420 PZN1 H RSJ 800 PZN1 H 3 Nomenclature RSJ 420 S Z N1 H H type Refrigerant type N1 R410A...

Page 5: ...z Technical Manual MCAC HTSM 201506 5 Part 2 Performance 1 Features 6 2 Specifications 7 3 Dimensions Unit mm 9 4 Service Space Unit mm 11 5 Refrigerant circuit 13 6 Wiring Diagrams 15 7 Electric Char...

Page 6: ...orb Refrigerant E heater design can ensure that hot water can be produced stably during defrosting period Multi protection High and low pressure protection over load current protection anti freezing f...

Page 7: ...ntrol EXV Fan Type Axial fan Motor model YDK550 6E Motor brand Yongan Dayang Welling Matchwell Quantity 1 Motor input W 810 680 Capacitor 25 F 450V Speed Hi lo r min 850 750 Coil Type Copper tube and...

Page 8: ...55 C Model RSJ 800 SZN1 H Power supply 380 415V 3Ph 50Hz Water heating Capacity kW 80 0 Input kW 20 00 COP W W 4 00 Running ambient temperature 15 C 46 C Outlet water temperature Default 56 C 40 C 60...

Page 9: ...Refrigerant oil ml 3 300 Controller KJR 51 BMKE A Wired controller Air flow m 3 h 25 000 Water pipe Inlet pipe mm DN50 Outlet pipe mm DN50 Hot water yield m 3 h 1 72 Dimension W H D mm 1 015 1 775 1...

Page 10: ...MCAC HTSM 201506 Midea R410A Direct Heating Commercial Heat Pump 50Hz Technical Manual 10 RSJ 800 SZN1 H Top view...

Page 11: ...Midea R410A Direct Heating Commercial Heat Pump 50Hz Technical Manual MCAC HTSM 201506 11 4 Service Space Unit mm RSJ 420 SZN1 H...

Page 12: ...MCAC HTSM 201506 Midea R410A Direct Heating Commercial Heat Pump 50Hz Technical Manual 12 RSJ 800 SZN1 H...

Page 13: ...Midea R410A Direct Heating Commercial Heat Pump 50Hz Technical Manual MCAC HTSM 201506 13 5 Refrigerant circuit RSJ 420 SZN1 H...

Page 14: ...MCAC HTSM 201506 Midea R410A Direct Heating Commercial Heat Pump 50Hz Technical Manual 14 RSJ 800 SZN1 H...

Page 15: ...Midea R410A Direct Heating Commercial Heat Pump 50Hz Technical Manual MCAC HTSM 201506 15 6 Wiring Diagrams RSJ 420 SZN1 H...

Page 16: ...pressure protection connector 3 System high pressure protection connector 4 E heater Temp Sensor of refrigerant connector 5 Water tank pook Temp sensor connector only the host is valid the slave is in...

Page 17: ...c control function Set the host unit through the address dial code on electric control board Stipulate the unit with address dial code 0 as the host unit Only after setting the host unit the function...

Page 18: ...er pump control right side E heater control Only supply ON OFF signal not supply power signal 28 Right side Remote alarm signal output Only supply non source ON OFF signal not supply power signal 29 E...

Page 19: ...Midea R410A Direct Heating Commercial Heat Pump 50Hz Technical Manual MCAC HTSM 201506 19 RSJ 800 SZN1 H...

Page 20: ...s valid the slave is invalid 6 Water outlet Temp sensor connector 7 E heater pipe Temp sensor connector of refrigerant 8 Water inlet Temp sensor connector 9 Discharge Temp sensor connector 10 Suction...

Page 21: ...ing the operating state of unit Right side FORCE constraint button special function for constraint exit 16 Digital screen 17 3 phase 4 wire system power input Lack of phase or wrong phase only is dete...

Page 22: ...boards Here only explains one PCB board 7 Electric Characteristics Model RSJ 420 SZN1 H RSJ 800 SZN1 H Outdoor unit Hz 50 50 Voltage 380 415V 3Ph 380 415V 3Ph Min 342V 342V Max 456V 456V Power supply...

Page 23: ...5 05 55 48 02 4 75 60 47 19 4 31 30 15 40 46 63 5 65 45 46 31 5 32 50 45 86 4 99 55 47 61 4 68 60 45 03 4 45 25 15 40 42 04 5 09 45 42 62 4 86 50 42 72 4 60 55 44 28 4 34 60 42 49 3 93 20 15 40 41 15...

Page 24: ...6 50 94 60 4 76 55 94 04 4 49 60 92 81 4 21 30 15 40 88 94 5 30 45 88 62 5 00 50 88 17 4 68 55 87 70 4 39 60 87 34 4 16 25 15 40 83 06 4 86 45 83 64 4 64 50 83 74 4 39 55 83 70 4 15 60 83 51 3 92 20 1...

Page 25: ...Qty Purpose Installation operation manual 1 Water tank temperature sensor 1 For water tank temperature inspection Wired controller 1 Control the unit and display unit status Wire harness matched with...

Page 26: ...01506 Midea R410A Direct Heating Commercial Heat Pump 50Hz Technical Manual 26 Part 3 Installation 1 Safety information 27 2 Unit Installation 28 3 Trial run 44 4 Fault analysis and solutions 46 5 Mai...

Page 27: ...manual Improper installation may result in water leakage electric shock or fire Ask qualified person for relocating repairing and maintaining the unit Improper installation may result in water leakage...

Page 28: ...not operate the unit with a wet hand An electric shock may be caused The installation height of power supply should be over 1 8m if there is any water spattered separate the power supply from water A...

Page 29: ...MCAC HTSM 201506 29 2 1 Unit outlook RSJ 420 SZN1 H RSJ 800 SZN1 H 2 2 Carrying of unit Handling rope should at least can bear 3 times of the unit weight and must go through the handling holes shown...

Page 30: ...cess Unit gradient should be less than 3 Handle with care do not collide and drag drastically DO NOT stand in handling operating radius The distance between the air outlet mesh of unit and lift hook s...

Page 31: ...not be connected to the foundation of the building to avoid affecting the people due to transfer of noise and vibration The base of the unit is provided with installation holes which can be used to c...

Page 32: ...Midea R410A Direct Heating Commercial Heat Pump 50Hz Technical Manual 32 RSJ 800 SZN1 H 2 5 Unit installation space Ensure enough space for installation and maintenance RSJ 420 SZN1 H Unit mm RSJ 800...

Page 33: ...turbulence disturbs air inlet If short walls are applied it should be shorter than the unit Distance between short walls or louvers to unit should either satisfy requirements of unit installation min...

Page 34: ...er into the pipeline system during the pipeline installation and connection The water flow switch which is used to detect the circulating water flow volume should be prepaired in site The cut off valu...

Page 35: ...f water pipe system Icon specifications Stop valve Motor operated valve Flexible rubber joint soft connect Water pump Water using end Water supply controller Solenoid valve Pressure reducing valve Ref...

Page 36: ...MCAC HTSM 201506 Midea R410A Direct Heating Commercial Heat Pump 50Hz Technical Manual 36 Double units drawing RSJ 800 SZN1 H Single unit drawing...

Page 37: ...erature sensor T5 can not be placed in the water or on the water pipe directly The water tank must be set a temperature pipe where the temperature sensor T5 is installed The water tank must have some...

Page 38: ...head of circulative pump On way resistance Local resistance Unit resistance Rated flow of circulative pump Rated flow of a single circulation heating unit Circulating unit quantity 2 8 E heater capac...

Page 39: ...ent Power supply wire and signal wire should be arranged properly without interruption to each other do not contact with connecting pipes and valves as well When strong electricity and weak electricit...

Page 40: ...5mm2 Manual switch Capacity 125A Fuse 100A Leakage protector 30mA 0 1sec below Specifications of controlling wire Item Size UL1015 Remarks E heater controlling wire 18 2 core Circulating water pump co...

Page 41: ...Midea R410A Direct Heating Commercial Heat Pump 50Hz Technical Manual MCAC HTSM 201506 41 Multi units RSJ 420 SZN1 H RSJ 800 SZN1 H...

Page 42: ...MCAC HTSM 201506 Midea R410A Direct Heating Commercial Heat Pump 50Hz Technical Manual 42 Electric wiring figure Electric control schematic diagram of the unit Only for reference...

Page 43: ...sor starts normally The water flow switch water pump ON OFF singal and E heater are only connected with the host unit which are not 220V control signal So do not directly drive loading When the host u...

Page 44: ...t RSJ 800 SZN1 H then it will invalid Each module of water heat pump has the electric control function Set the host unit through the address dial code on electric control board Stipulate the unit with...

Page 45: ...re normal 2 Whether the input voltage of the unit meet the requirements of the unit 3 Whether the electronic lock has been unlocked 4 Whether the water outlet temperature is normal 5 Whether there is...

Page 46: ...temperature fluctuation which is a normal phenomenon and will not affect the actual use appropriately adjust the water pressure can improve this phenomenon Water outlet temperature cannot reach the se...

Page 47: ...to drive Possible reason Detect and settle measure 1 Power errors Connected with wrong phase sequence 2 Wire connection is loosening Check and fasten again 3 Relay or fuse errors Check and repair 4 Co...

Page 48: ...device Compressor operated with no heating Possible reason Detect and settle measure 1 Refrigerant leakage Check repair and replenish the refrigerant 2 Compressor error Change the compressor No obvio...

Page 49: ...rror of EEprom 13 P0 System low pressure protection 14 P1 System high pressure protection 15 P2 Compressor current of system is overload Protection 16 P4 Protection for discharge Hi temperature Tp 115...

Page 50: ...he main unit with T5 situation display T5 temperature if without T5 or T5 error the unit will display error the slave unit will display the T1 temperature Detail spot check display contents as followi...

Page 51: ...ect and circulate heating for closed tank with 50Hz model 3A01 20 Protection frequency XY X for stop frequency because of 4 protections within 2 hours Y for protection frequency within 2 hours 21 Prot...

Page 52: ...ea R410A Direct Heating Commercial Heat Pump 50Hz Technical Manual 52 E2 Communication error of host unit and wired controller main unit and slave unit E8 Error of circulating water flow detector Only...

Page 53: ...e sensor in the water tank only host unit displays T5 E5 Error of air heat exchanger temperature sensor T3 E6 Error of outdoor ambient temperature sensor T4 E7 Error of E heater pipe temperature senso...

Page 54: ...MCAC HTSM 201506 Midea R410A Direct Heating Commercial Heat Pump 50Hz Technical Manual 54 P0 System low pressure protection...

Page 55: ...Midea R410A Direct Heating Commercial Heat Pump 50Hz Technical Manual MCAC HTSM 201506 55 P1 System high pressure protection...

Page 56: ...MCAC HTSM 201506 Midea R410A Direct Heating Commercial Heat Pump 50Hz Technical Manual 56 P2 Compressor current of system is overload Notes the value of Io is 30A...

Page 57: ...Midea R410A Direct Heating Commercial Heat Pump 50Hz Technical Manual MCAC HTSM 201506 57 P4 Protection for discharge Hi temperature Tp 115 C...

Page 58: ...it is not matched with wired controller host unit will display P7 and wired controller will display E2 Power supply of wired controller is 10VAC if the power supply is not stable the code of protectio...

Page 59: ...the unit When the heat exchanger has dust it should be immediately cleaned in case to affect the unit capacity or cause the unit stops for the protection Periodically clean the filter in the water sys...

Page 60: ...bonate or other minerals when these substances on the heat transfer surface scale is large then can affect the heat transfer performance and lead to increased power consumption high air exhaust pressu...

Page 61: ...Technical Manual MCAC HTSM 201506 61 PH value Total hardness Electrical conductivity Sulphate ion 6 5 8 0 50ppm 200 s cm 25 C 50ppm Silicon Iron content Sulfide ion Chloride ion 30ppm 0 3ppm None 50pp...

Page 62: ...MCAC HTSM 201506 Midea R410A Direct Heating Commercial Heat Pump 50Hz Technical Manual 62 Part 4 Controller 1 Wired Controller Standard 63...

Page 63: ...es 1 Touch key operation 2 LCD displays operation parameters 3 Multiple timers 4 Real time clock battery life 5 8 years 1 2 Introduction of function buttons on the wired controller The wired controlle...

Page 64: ...ays when check function is on Displays when ambient temperature is below 2 C which means the main unit need anti freezing action Displays when no key operation for 2 minutes and all keys are locked Pr...

Page 65: ...Setting water temperature timing and mode etc Press and hold this key for 3 seconds to enter check status 14 Add and Reduce key and Move up or move down values of temperature timing water level etc T...

Page 66: ...in the dotted line frame are not general setting The wired controller automatically judges the needed setting according to the model of main unit Setting water temperature Press the or button to adju...

Page 67: ...means the current setting is the hour of Timer 1 on press the or to adjust press key when finished and then the minute of the clock will flash which means the current setting is the minute of Timer 1...

Page 68: ...mer 1 Similarly the setting of Timing 3 is the same as this method After setting is finished press OK key or wait for 7 seconds to confirm the setting and the LCD will display the effective timing inf...

Page 69: ...Set the cycle heating water temperature Reserved Continuous press SET key 3 times to enter cycle heating water temperature setting The LCD will display SET CYCLE WATER TEMP and temperature value will...

Page 70: ...ould be correct otherwise cannot get the correct timing on and timing off Set water level Reserved Press the SET key 5 times to enter the water level setting Press the or key to adjust the water level...

Page 71: ...to run the main water pump in the device installing and debugging Operation method Press AUXILIARY key 3 times to enter this function The icon will flash and then press OK key to confirm The PUMP ico...

Page 72: ...ormation from 0 15 Press or to adjust the check sequence number of one unit and check all the status information of this unit Check content Water outlet temperature T1 2 Outdoor pipe temperature T3 3...

Page 73: ...ual to the user Reinstallation must be performed by professional Do not install the unit in a place vulnerable to leakage of flammable gases Once flammable gases are leaked and left around the wired c...

Page 74: ...ks Wired controller 1 Cross round head wood mounting screw 3 M4 20 for mounting on the wall Cross round head mounting screw 2 M4 25 for mounting on the electric switch box Installation manual 1 Owner...

Page 75: ...two methods to connection between wired controller and main unit 1 4 5 Back cover installation Use straight head screwdriver to insert into the buckling position in the bottom of wired controller and...

Page 76: ...ust the length of two plastic screw bars in the accessory to be standard length from the electrical box screw bar to the wall Make sure when install the screw bar to the electrical box screw bar make...

Page 77: ...l Manual MCAC HTSM 201506 77 Over fasten the screw will lead to deformation of back cover 1 4 6 Wire outlet Avoid the water enter into the wired controller use trap and putty to seal the connectors of...

Page 78: ...Front cover installation After adjusting the front cover and then buckle the front cover It should avoid to clamping the communication switching wire during installation Correct install the back cove...