V6-i VRF 50/60Hz
107
P
art
6
- Di
agno
si
s and
Tr
ou
bles
ho
o
ting
2.15
H8: High pressure sensor error
Digital display output
2.15.1
Description
2.15.2
High pressure sensor error.
All units stop running.
Error code is only displayed on the unit with the error.
Trigger / recover condition
2.15.3
Trigger condition: Discharge pressure ≤ 0.3MPa.
Recover condition: Discharge pressure > 0.3MPa.
Reset method: Resume automatically.
Possible causes
2.15.4
Outdoor unit stop valves are closed.
Pressure sensor not connected properly or has malfunctioned.
Insufficient refrigerant.
Low pressure side blockage.
Poor evaporator heat exchange.
Main PCB damaged.