33
10.1 Indoor Unit Error Display
Display LED
STATUS
E0/EA
Indoor unit EEPROM parameter error
E1
Indoor / outdoor units communication error
E3
Indoor fan speed is operating outside of the normal range
E4
Indoor room temperature sensor T1 open circuit or short circuit
E5
Evaporator coil temperature sensor T2 open circuit or short circuit
EC
Refrigerant leakage detection
Eb
Communication error between the indoor PCB and display board
F0
Overload current protection
F1
Outdoor ambient temperature sensor T4 open circuit or short circuit
F2
Condenser coil temperature sensor T3 open circuit or short circuit
F3
Compressor discharge temperature sensor T5 open circuit or short circuit
F4
Outdoor unit EEPROM parameter error
F5
Outdoor fan spe
ed is operating outside of the normal range
P0
IPM malfunction or IGBT over-strong current protection
P1
Over or low voltage protection
P2
High temperature protection of IPM module
P4
Inverter compressor drive error
Trouble shooting:
Use the remote controller. If the unit does not respond to the remote, the indoor PCB needs to be
replaced; if the unit does respond, then the display board needs to be replaced.