43
8.4.3.5 High evaporator coil temp.T2 protection
For 7k,9k,12k,16k,17k,18k models:
For 21k,24k models:
8.4.4 Auto-mode
The machine will choose cooling, heating or fan-
only mode according to ΔT (ΔT =T1
-Ts).
ΔT=T1
-Ts
Running mode
ΔT
>2
℃
Cooling
-1
℃
≤ΔT≤2
℃
Fan-only
ΔT<
-1
℃
Heating
(for cooling only models, they will run at fan-only
mode)
AC will run in auto mode in the below cases:
(
1
)
Pressing the forced auto button.
(
2
)
If AC is off, it will run in auto mode when the timer on function is active.
(
3
)
After setting the mode, AC will run in auto mode if the compressor keeps not running for 15
minutes.
8.4.5 Drying mode
For 7k,9k,12k,16k,17k,18k models:
8.4.5.1 The indoor fan will run following the action of the compressor. If the compressor is on, the
indoor fan will run at low speed. If the compressor is off, the indoor fan will run at breeze.
Summary of Contents for MOA-11HN1-QB8
Page 1: ...LUNA ON OFF SERIES Service Manual 2014 9ASEU B1 1401...
Page 16: ...14 MS9A 12HRN1 QC7G...
Page 17: ...15 MS9A 18HRN1 QC5...
Page 18: ...16 MS9A 24HRN1 QB8W...
Page 20: ...18 MOC 17HN1 QC0...
Page 21: ...19 MOC 18HN1 QC0 MOF3 18HN1 QC5...
Page 22: ...20 MOP 24HN1 QB8W...
Page 23: ...21 MOF1 24HN1 QB8W...