Owner’s & Installation manual

With air release valve, the other side is water inlet pipe.

When connect water collecter, set the tightening torque to 

6180~7540N.cm(630~770kgf.cm), and use a spanner to 

tighten it as shown in Figure. 

The diameter of connective junction in water inlet pipe and 

water outlet pipe is RC3/4 tapper pipe thread inside.

The diameter of condensate pipe is ZG3/4 tapper pipe thread 

outside.      

8.    PIPES CONNECTION

Fig.8-1

9.    INSTALLATING DRAINAGE PIPE

Install the drain pipe of the fan coil unit

Before out from factory, the scupper adopts the pipe thread.  

Be sure to perform heat insulation for the drain pipe of the 

indoor unit. Otherwise, condensate will occur. The joint of the 

indoor unit should also undergo heat insulation treatment. 

When performing the pipes connection, use the rigid PVC 

binder, and make sure that no leak exists. 

Same as the joint of the indoor unit. Be careful not to apply 

force at the pipe side of the indoor unit. 

The downward gradient of the drain pipe should be higher 

than (1/100), without bend in the middle. 

The total length of the drain pipe when pulled out traversely 

shall not exceed 20m, when the pipe is over long, a prop 

stand must be installed prevent winging. 

NOTE

Fig.9-1

Heat insulation 

      materials

1.5m~2m

Downward gradient 

is over 1/100

The centralized pipes should be distributed against the figure

shown on the right side. 

Drain test

Before the test, ensure that the drain pipes are smooth and 

the adapters are sealed. 

Newly built rooms should undergo the drain test before the 

ceiling is laid.        

Fig.9-3

Fig.9-2

Bend

S-shape 

As large as practicable (approx. 10cm)

Downward gradient 

is over 1/100

Summary of Contents for MKT2-V1000

Page 1: ...oil Unit Of Duct Type OWNER S INSTALLATION MANUAL Thank you very much for purchasing our air conditioner Before using your air conditioner please read this manual carefully and keep it for future refe...

Page 2: ......

Page 3: ...parts and specified parts for installation otherwise it will cause the set to fall water leakage electrical shock and fire The appliance must be installed 2 3m above floor The appliance shall not be i...

Page 4: ...revent image interference or noise Depending on the radio waves a distance of 1 meter may not be sufficient enough to eliminate the noise This appliance can be children aged from 8 yeas and above and...

Page 5: ...h the construction and fit out staff Scope of dismantling the ceiling Please keep the ceiling horizontal Reinforce the beams and girders of the ceiling lest vibration of the ceiling Cut off the beams...

Page 6: ...cause water leak Connect the duct The duct length is determined according to the external static pressure Install the wire control switch For installation of the wire control switch see the installat...

Page 7: ...eiling by a rope 7 3 Connect the accessional plastic water tray no air return box type without Fig 7 10 Four pipe type unit mm Table 7 1 The quantities of the fans and motors are only for reference pl...

Page 8: ...ergo heat insulation treatment When performing the pipes connection use the rigid PVC binder and make sure that no leak exists Same as the joint of the indoor unit Be careful not to apply force at the...

Page 9: ...n fixed wiring The appliance shall be installed in accordance with national wiring regulations Be sure to locate the power wiring and the signal wring well to avoid cross disturbance Do not turn on th...

Page 10: ...CN1 CN5 MAIN BOAD MOTOR2 CN8 SW1 SW2 ON OFF S8 ON S6 OFF S7 S4 S5 YELLOW GREEN EARTH L HI MID LOW N N YELLOW GREEN POWER IN CN3 YELLOW BLUE RED BLACK Live wire Nuetral wire Ground wire Three speed swi...

Page 11: ...otor single m otor single m otor single m otor double m otor double m otor Not set models 10 2 The default model of DC fan coil is set as 12Pa when leaving the factory Clients can dial to the respond...

Page 12: ...A 51 44 35 dB contact details Information to identify the model s to w hich the information relation MODE MKT2 V300 Item Symbol Value Unit Cooling capacity sensible Prated c 2 82 kW Cooling capacity l...

Page 13: ...formation to identify the model s to w hich the information relation MODE MKT2 V800 Item Symbol Value Unit Cooling capacity sensible Prated c 6 67 kW Cooling capacity latent Prated c 1 25 kW Heating c...

Page 14: ...WA 50 44 37 dB contact details Information to identify the model s to w hich the information relation MODE MKT3 V300 Item Symbol Value Unit Cooling capacity sensible Prated c 3 1 kW Cooling capacity l...

Page 15: ...rmation to identify the model s to w hich the information relation MODE MKT3 V800 Item Symbol Value Unit Cooling capacity sensible Prated c 7 33 kW Cooling capacity latent Prated c 1 63 kW Heating cap...

Page 16: ...WA 50 44 35 dB contact details Information to identify the model s to w hich the information relation MODE MKT4 V300 Item Symbol Value Unit Cooling capacity sensible Prated c 3 09 kW Cooling capacity...

Page 17: ...nformation to identify the model s to w hich the information relation MODE MKT4 V800 Item Symbol Value Unit Cooling capacity sensible Prated c 6 66 kW Cooling capacity latent Prated c 1 38 kW Heating...

Page 18: ...45 0 38 7 dB contact details MODE MKT3 V300F Information to identify the model s to w hich the information relation Item Symbol Value Unit Cooling capacity sensible Prated c 2 445 kW Cooling capacity...

Page 19: ...2 52 2 44 4 dB contact details Information to identify the model s to w hich the information relation MODE MKT3 V800F Item Symbol Value Unit Cooling capacity sensible Prated c 6 036 kW Cooling capacit...

Page 20: ...16126200000003 V4 0...

Page 21: ...e ground wire is charged If it is the unit shall not be installed before correction 3 Before installing the unit be sure to confirm with the user whether there are wires water pipes air pipes and so o...

Reviews: