MCAC-TSM-2008-02
Electrical Connection
Installation
73
It consists of a remote control module.
To install the kit, proceed as follows:
- disconnect the power supply and then access the inside f the electrical panel;
- connect the remote control module with 3 wires to terminals 15, 16 and 17 on the installer terminal board:
connect terminal 15 to terminal
Black/gnd
on the module;
connect terminal 16 to terminal
Blue/signal
on the module;
connect terminal 17 to terminal
Red/+12v
on the module;
Important
To avoid interference due to magnetic fields, the use of shielded cable is recommended. The cable should
not be more than 100m long.
The Specification of Power:
Type MGC-F05W/N1
MGC-F07W/N1
MGC-F09W/N1
MGC-F10W/N1
Power
220~240-1-50 220~240-1-50 220~240-1-50 220~240-1-50
Circuit breaker/fuse (A)
25/20 30/25 40/25 40/35
Power wiring (mm
2
)
3×2.5 3×2.5 3×4.0 3×4.0
Ground wiring (mm
2
)
2.5 2.5 4.0 4.0
Outdoor /Indoor connecting wiring (mm
2
) 1.0 1.0 1.0 1.0
Type MGC-F10W/SN1
MGC-F12W/SN1
MGC-F14W/SN1 MGC-F16W/SN1
Power
380~415-3-50 380~415-3-50 380~415-3-50 380~415-3-50
Circuit breaker/fuse (A)
25/15 25/15 25/15 30/20
Power wiring (mm
2
)
5×2.5 5×2.5 5×2.5 5×4.0
Ground wiring (mm
2
)
2.5 2.5 2.5 4.0
Outdoor /Indoor connecting wiring (mm
2
)
1.0 1.0 1.0 1.0
Important
The power cord type designation is H07RN-F.
Connecting cable between indoor unit and outdoor unit shall be approved poly-chloroprene sheathed flexible
cord, type designation H07RN-F or heavier cord.
The means for disconnection from a power supply shall be incorporated in the fixed wiring and have an air
gap contact separation of at least 3mm in each active(phase) conductors.
Summary of Contents for MGC-F05W/N1
Page 2: ......
Page 15: ...MCAC TSM 2008 02 Outdoor units Outdoor units 13 2 2 MGC F09W N1 MGC F10W N1 MGC F10W SN1...
Page 16: ...Specification MCAC TSM 2008 02 14 Installation 2 3 MGC F12W SN1 MGC F14W SN1 MGC F16W SN1...
Page 19: ...MCAC TSM 2008 02 Outdoor units Outdoor units 17 5 Wiring Diagrams 5 1 MGC F05W N1 MGC F07W N1...
Page 20: ...Specification MCAC TSM 2008 02 18 Installation 5 2 MGC F09W N1 MGC F10W N1...
Page 39: ...MCAC TSM 2008 02 Outdoor units Outdoor units 37 8 Operation Limits...
Page 42: ...Specification MCAC TSM 2008 02 40 Installation 10 Exploded View 10 1 MGC F05W N1...
Page 44: ...Specification MCAC TSM 2008 02 42 Installation 10 2 MGC F07W N1...
Page 46: ...Specification MCAC TSM 2008 02 44 Installation 10 3 MGC F09W N1 MGC F10W N1...
Page 48: ...Specification MCAC TSM 2008 02 46 Installation 10 4 MGC F10W SN1...
Page 50: ...Specification MCAC TSM 2008 02 48 Installation 10 5 MGC F12W SN1 MGC F16W SN1...
Page 52: ...Specification MCAC TSM 2008 02 50 Installation 10 6 MGC F14W SN1...
Page 86: ...Standard Controller MCAC TSM 2008 02 84 Controller 3 Select the Clock CL...
Page 89: ...MCAC TSM 2008 02 Standard Controller Controller 87...
Page 94: ...Standard Controller MCAC TSM 2008 02 92 Controller...