MCAC-TSM-2008-02
Outdoor units
Outdoor units
53
2. Er01
High pressure
>
4.4MPa, display Er01, compressor and outdoor fan stop, the chiller can only resume
from protection manually.
Values display indication Er01
Refer to the instruction manual: High pressure protection
Judge 1: check the high pressure switch is well.
Replace the high pressure switch
No
Judge 2: Whether the temperature of external and inlet water is high
Check the operation conditions:
1. the temperature of inlet water (cooling: below 20 ,
℃
heating: below 45 )
℃
2. cooling: the indoor temperature is
≥
17 and the
℃
ambient temperature is 10
℃
~
43
℃
3. heating: the indoor temperature is
≤
30 and the
℃
outdoor temperature is -15
℃
~
24
℃
Stop the operation, and run it
at the normal condition.
No
Yes
Judge 3: Whether the refrigerant charge is excessive.
Check the temperature of compressor discharge and suction and
the pressure of compressor discharge and suction are normal.
Reclaim part of refrigerant
Yes
Judge 4: Whether the air flow and water flow
are insufficient
Cooling: Check whether the speed of the fan
are normal. Heating: Check whether the water flow
volume can reach the data as follow :
Capacity
( kW)
Water flow
volume (m
3
/h)
Capacity
( kW)
Water flow
volume (m
3
/h)
5 0.86 10 1.72
7 1.24 12 2.0
9 1.54 14 2.4
10 1.74 16 2.8
Change the fan or pump.
No
No
Judge 5: PCB is malfunction.
Replace PCB
Yes
Yes
Summary of Contents for MGC-F05W/N1
Page 2: ......
Page 15: ...MCAC TSM 2008 02 Outdoor units Outdoor units 13 2 2 MGC F09W N1 MGC F10W N1 MGC F10W SN1...
Page 16: ...Specification MCAC TSM 2008 02 14 Installation 2 3 MGC F12W SN1 MGC F14W SN1 MGC F16W SN1...
Page 19: ...MCAC TSM 2008 02 Outdoor units Outdoor units 17 5 Wiring Diagrams 5 1 MGC F05W N1 MGC F07W N1...
Page 20: ...Specification MCAC TSM 2008 02 18 Installation 5 2 MGC F09W N1 MGC F10W N1...
Page 39: ...MCAC TSM 2008 02 Outdoor units Outdoor units 37 8 Operation Limits...
Page 42: ...Specification MCAC TSM 2008 02 40 Installation 10 Exploded View 10 1 MGC F05W N1...
Page 44: ...Specification MCAC TSM 2008 02 42 Installation 10 2 MGC F07W N1...
Page 46: ...Specification MCAC TSM 2008 02 44 Installation 10 3 MGC F09W N1 MGC F10W N1...
Page 48: ...Specification MCAC TSM 2008 02 46 Installation 10 4 MGC F10W SN1...
Page 50: ...Specification MCAC TSM 2008 02 48 Installation 10 5 MGC F12W SN1 MGC F16W SN1...
Page 52: ...Specification MCAC TSM 2008 02 50 Installation 10 6 MGC F14W SN1...
Page 86: ...Standard Controller MCAC TSM 2008 02 84 Controller 3 Select the Clock CL...
Page 89: ...MCAC TSM 2008 02 Standard Controller Controller 87...
Page 94: ...Standard Controller MCAC TSM 2008 02 92 Controller...