R410A tropical air-cooled scroll chiller unit 60Hz MCAC-ATSM-2014-09
94
12.2.8 Diameter parameters of main inlet and outlet pipes
Table of diameter parameters of main inlet and outlet pipes for 30kW module
Unit model x quantity
Total inlet and outlet water
pipe diameter
Unit model x quantity
Total inlet and outlet water
pipe diameter
30×1
DN40
30×9
DN100
30×2
30×10
30×3
DN65
30×11
30×4
30×12
DN125
30×5
30×13
30×6
DN80
30×14
30×7
30×15
30×8
30×16
Table of diameter parameters of main inlet and outlet pipes for 60kW module
Unit model x quantity
Total inlet and outlet water
pipe diameter
Unit model x quantity
Total inlet and outlet water
pipe diameter
60×1
DN65
60×9
DN125
60×2
60×10
60×3
DN80
60×11
DN150
60×4
DN100
60×12
60×5
60×13
60×6
60×14
60×7
DN125
60×15
DN200
60×8
60×16
Table of diameter parameters of main inlet and outlet pipes for 120kW module
Unit model x quantity
Total inlet and outlet water
pipe diameter
Unit model x quantity
Total inlet and outlet water
pipe diameter
120×1
DN65
120×5
DN125
120×2
DN80
120×6
DN150
120×3
DN100
120×7
DN150
120×4
DN125
120×8
DN200
Table of diameter parameters of main inlet and outlet pipes for 180kW module
Unit model x quantity
Total inlet and outlet water
pipe diameter
Unit model x quantity
Total inlet and outlet water
pipe diameter
180×1
DN80
180×4
DN150
180×2
DN100
180×5
DN200
180×3
DN125
Please pay attention to the following items when installing multiple modules:
● Each module corresponds to an address code which can’t be repeated.
● Main water outlet temperature sensing bulb, target flow controller and auxiliary electric heater are under
control of the main module.
● One wired controller and one target flow controller are required and connected on the main module.
● The unit can be started up through the wired controller only after all addresses are set and the
aforementioned items are determined. The wired controller is
≤500m away from the outdoor unit.
12.2.9 Chilled water flow
Minimum chilled water flow
The minimum chilled water flow is shown in the below table.
If the system flow is less than the minimum unit flow rate, the evaporator flow can be recalculated, as shown
in the diagram.
Summary of Contents for MGBT-F120W/PN1
Page 28: ...MCAC ATSM 2014 09 R410A tropical air cooled scroll chiller unit 60Hz 29 60kW module ...
Page 29: ...R410A tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 30 120kW module ...
Page 30: ...MCAC ATSM 2014 09 R410A tropical air cooled scroll chiller unit 60Hz 31 180kW module ...
Page 32: ...MCAC ATSM 2014 09 R410A tropical air cooled scroll chiller unit 60Hz 33 60kW module ...
Page 33: ...R410A tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 34 120kW module ...
Page 34: ...MCAC ATSM 2014 09 R410A tropical air cooled scroll chiller unit 60Hz 35 180kW module ...
Page 36: ......
Page 46: ...MCAC ATSM 2014 09 R410A tropical air cooled scroll chiller unit 60Hz 47 ...
Page 48: ...MCAC ATSM 2014 09 R410A tropical air cooled scroll chiller unit 60Hz 49 MGCT D30W PN1 ...
Page 49: ...R410A tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 50 ...
Page 51: ...R410A tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 52 10 2 MGBT F60W PN1 ...
Page 54: ...MCAC ATSM 2014 09 R410A tropical air cooled scroll chiller unit 60Hz 55 ...
Page 55: ...R410A tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 56 ...
Page 57: ...R410A tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 58 10 4 MGBT F180W PN1 ...
Page 82: ...MCAC ATSM 2014 09 R410A tropical air cooled scroll chiller unit 60Hz 83 ...