Floor Standing MFM
DM16-01.01.25en
Service manual
40
TE6
T2
On
Off
TE5
When the evaporator coil temp.T2 keeps lower than TE5 for 30 minutes, the compressor and
outdoor fan will shut off. When T2 is higher than TE6, the compressor and outdoor fan will restart
up.
Condition 2:
TE6
T2
On
Off
TE5-2
When the evaporator coil temp.T2 keeps lower than TE5-2 for 20 minutes, the compressor and
outdoor fan will shut off. When T2 is higher than TE6, the compressor and outdoor fan will restart
up.
Condition 3:
TE6
T2
On
Off
TE5-4
When the evaporator coil temp.T2 keeps lower than TE5-4 for 8 minutes, the compressor and
outdoor fan will shut off. When T2 is higher than TE6, the compressor and outdoor fan will restart
up.