10.1.3.3 The restart of the compressor shall execute the delay protection.
10.1.4 Condenser high temperature protection
10.1.4.1 Only available to cooling and dehumidifying mode.
10.1.4.2 Action condition
10.1.4.3 Delay protection should be performed when the compressor restarts.
10.1.5 Outdoor protection
When outdoor protection signal is high level(last 4 seconds), outdoor unit will perform
protection: the whole machine will be shut down while the indoor unit will indicate the
corresponding protection signal(Ed).
The A/C will recover if outdoor errors are eliminated after the outdoor protection occurs.
Condition
Outdoor fan
Compressor
T2
≤
2
°
C
(
last 3 minutes
)
Off
Off
T2
≥
7
°
C
On
On
Condition
Outdoor fan
Compressor
Condenser temp.
≥
65
°
C
(
last 3 seconds
)
Off
Off
Condenser temp.<52°C
On
On