21
6).When the electronic scale displays the proper weight (refer to the gauge and the
pressure of the low side), disconnect the charge hose from the 3-way valve’s service port
immediately and turn off the air conditioner before disconnecting the hose.
7). Mount the valve stem caps and the service port
Use torque wrench to tighten the service port cap to a torque of 18N.m.
Be sure to check for gas leakage.