Capacity Tables
MCAC-UTSM-2009-03
12
Indoor Units
6.3 MFA-12HRN1-Q
Cooling capacity
Cooling
Outdoor conditions (DB)
Indoor Conditions
(kW)
21ºC
28ºC
35ºC
43ºC
21/15ºC DB/WB
TC 3.30
3.14
2.98
2.85
SC 2.44
2.41
2.38
2.39
Input 0.91
0.99
1.03
1.07
24/17ºC DB/WB
TC 3.39
3.23
3.07
2.88
SC 2.54
2.52
2.49
2.42
Input 0.97
1.03
1.08
1.13
27/19ºC DB/WB
TC 3.46
3.30
3.21
2.98
SC 2.56
2.54
2.50
2.44
Input 0.99
1.05
1.101
1.16
32/23ºC DB/WB
TC 3.52
3.39
3.33
3.07
SC 2.99
2.95
2.93
2.86
Input 1.03
1.08
1.16
1.20
Heating capacity
Heating Outdoor
conditions
Indoor Conditions (DB)
(kW)
24/18ºC DB/WB
7/6ºC DB/WB
2/1ºC DB/WB
-5/-6ºC DB/WB
15ºC
TC 4.58 3.70 3.03 2.75
Input 1.21
1.04 0.89 0.84
20ºC
TC 4.44 3.68 2.85 2.68
Input 1.32 1.117 0.98 0.90
27ºC
TC 4.15 3.31 2.68 2.60
Input 1.40
1.21 1.06 0.98
Remark:
TC: Total capacity; kW
SC: Sensible heat capacity; kW
Input: Input power; kW
Summary of Contents for MFA-12HRN1
Page 2: ......
Page 9: ...MCAC UTSM 2009 03 Dimensions Indoor Units 7 2 Dimensions 3 Service Space...
Page 23: ...MCAC UTSM 2009 03 Wiring Diagrams Outdoor Units 21 5 Wiring Diagrams 5 1 MON 12HN1...
Page 24: ...Wiring Diagrams MCAC UTSM 2009 03 22 Outdoor Units 5 2 MON 18HN1...
Page 25: ...MCAC UTSM 2009 03 Wiring Diagrams Outdoor Units 23 5 3 MON 12HN1 Q...
Page 55: ...MCAC UTSM 2009 03 Wiring Installation 53 6 2 3 Wiring figure...
Page 58: ...Control MCAC UTSM 2009 03 56 Control Part 5 Control 1 Wireless remote controller R51D E 57...