MCAC-VTSM-2014-09
R410A All DC Inverter Mini VRF
Specifications & Performance 31
MDV-V120W/DVN1
Cooling
Combination
(%)
(Capacity
index)
Outdoor
temperature
(°F DB)
Indoor temperature(°FDB/WB)
DB:69.4,WB:57.2
DB:73.9,WB:60.8
DB:78.4,WB:64.4
DB:80.6,WB:66.2
DB:82.7,WB:68
DB:87.3,WB:71.6
DB:89.6,WB:75.2
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
50%
23
4.05
0.53
4.84
0.61
5.61
0.7
6
0.73
6.39
0.77
7.16
0.88
7.97
0.95
28.4
4.05
0.53
4.84
0.62
5.61
0.71
6
0.74
6.39
0.79
7.16
0.89
7.97
0.96
32
4.05
0.54
4.84
0.63
5.61
0.72
6
0.75
6.39
0.79
7.16
0.9
7.97
0.98
35.6
4.05
0.55
4.84
0.64
5.61
0.73
6
0.76
6.39
0.81
7.16
0.91
7.97
0.99
39.2
4.05
0.55
4.84
0.65
5.61
0.74
6
0.77
6.39
0.82
7.16
0.93
7.97
1.02
42.8
4.05
0.56
4.84
0.66
5.61
0.75
6
0.79
6.39
0.84
7.16
0.95
7.97
1.05
46.4
4.05
0.58
4.84
0.67
5.61
0.76
6
0.81
6.39
0.85
7.16
0.96
7.97
1.08
50
4.05
0.59
4.84
0.68
5.61
0.78
6
0.82
6.39
0.88
7.16
0.99
7.97
1.1
53.6
4.05
0.59
4.84
0.69
5.61
0.79
6
0.84
6.39
0.89
7.16
1
7.97
1.12
57.2
4.05
0.6
4.84
0.7
5.61
0.8
6
0.85
6.39
0.91
7.16
1.02
7.97
1.14
60.8
4.05
0.61
4.84
0.71
5.61
0.81
6
0.87
6.39
0.92
7.16
1.04
7.97
1.16
64.4
4.05
0.62
4.84
0.72
5.61
0.82
6
0.88
6.39
0.94
7.16
1.06
7.97
1.18
68
4.05
0.63
4.84
0.73
5.61
0.84
6
0.89
6.39
0.95
7.16
1.07
7.97
1.2
69.8
4.05
0.63
4.84
0.74
5.61
0.85
6
0.9
6.39
0.96
7.16
1.09
7.97
1.21
73.4
4.05
0.64
4.84
0.74
5.61
0.86
6
0.92
6.39
0.98
7.16
1.1
7.97
1.24
77
4.05
0.65
4.84
0.76
5.61
0.88
6
0.94
6.39
1.01
7.16
1.16
7.97
1.32
80.6
4.05
0.66
4.84
0.79
5.61
0.92
6
1
6.39
1.07
7.16
1.24
7.97
1.41
84.2
4.05
0.7
4.84
0.83
5.61
0.98
6
1.06
6.39
1.14
7.16
1.31
7.97
1.5
87.8
4.05
0.74
4.84
0.88
5.61
1.04
6
1.13
6.39
1.21
7.16
1.4
7.97
1.6
91.4
4.05
0.78
4.84
0.93
5.61
1.1
6
1.19
6.39
1.29
7.16
1.48
7.97
1.7
95
4.05
0.82
4.84
0.99
5.61
1.16
6
1.26
6.39
1.36
7.16
1.58
7.97
1.8
98.6
4.05
0.87
4.84
1.04
5.61
1.24
6
1.34
6.39
1.45
7.16
1.67
7.97
1.92
102.2
4.05
0.92
4.84
1.1
5.61
1.31
6
1.41
6.39
1.53
7.16
1.77
7.97
2.04
105.8
4.05
0.95
4.84
1.15
5.61
1.35
6
1.48
6.39
1.6
7.16
1.87
7.97
2.13
109.4
4.05
1.02
4.84
1.23
5.61
1.4
6
1.55
6.39
1.64
7.16
1.96
7.97
2.23
Note:
1
.
is tested under our standard condition.
2. Avoid to run the unit when the temperature is above 109.4
℉
(43
℃
).
3. The above table shows the average value of conditions may operate.
4. It is recommended to connect less than 130%.