26
I3COOL
I2COOL
Off
Decrease
Hold
Resume
I1COOL
I3COOL, I2COOL,I1COOL mean different
running current value.
Off: Compressor stops.
Decrease: Decrease the running frequency to
the lower level.
Hold: Keep the current frequency.
Resume: No limitation for frequency.
Note:
When AC is in “hold” zone for 3 minutes, the
compressor frequency will rise to the higher
level.(frequency will increase twice at most)
9.4.2.2 Outdoor fan running rules
22
20
High
Low
9.4.2.3 Indoor fan running rules
In cooling mode, indoor fan runs all the time
and the speed can be selected as high,
medium, low and auto.
Auto fan in cooling mode acts as follow:
4
3
High
Low
1
Medium
1.5
9.4.3 Heating Mode
9.4.3.1 Compressor running rules
The maximum operation frequency of the
compressor after starting submits to the
following rule.
Fmax=F3
Fmax=F5
Fmax=F7
Fmax=F9
Fmax=F10
Fmax=F8
Fmax=F6
Fmax=F2
34
Off
33
28
27
25
24
22
21
19
18
16
17
15
14
Fmax=F4
12
11
6
5
Fmax: The maximum operation frequency of
compressor.
F1~F8: The detailed value of the compressor
operation frequency.
If users switch on AC by remote controller, the
compressor will run at the Fmax frequency for 7
minutes according to outdoor ambient temp.
Summary of Contents for MCHS-09NIH1
Page 11: ...9 6 Wiring Diagram 6 1 Indoor Unit MEHS 09NiH1 MEHS 12NiH1 MEHS 09NiH2 MEHS 12NiH2 MEHS 18NiH2...
Page 12: ...10 MEHS 22NiH2...
Page 13: ...11 6 2 Outdoor Unit MCHS 09NiH1 MCHS 12NiH1...
Page 14: ...12 MCHS 09NiH2 MCHS 12NiH2...
Page 15: ...13 MCHS 18NiH2 MCHS 22NiH2...
Page 16: ...14 For MCHS 12NiH2 For MCHS 09NiH1 MCHS 12NiH1...
Page 17: ...15 For MCHS 09NiH2 For MCHS 18NiH2...
Page 18: ...16 For MCHS 22NiH2...
Page 50: ...48 P W P N...