MCAC-PDSM-2013-04                                                                    Midea Precision AC Technical Manual-Down Delivery Series 

23 

Outdoor coil 

(Single 

outdoor unit) 

No. of rows 

Tube pitch(a)×row pitch(b)     

mm 

25.4×22 

Fin spacing 

mm 

2.2 

Fin type 

Hydrophilic aluminum fin 

Pipe outside dia. and type 

mm 

Ф

9.52 

Inner grooved copper pipe 

Coil (W×D) 

mm 

1,250×914.4 

Number of circuits 

Indoor air flow 

m

3

/h 14,500 

Indoor external static pressure 

Pa 

20 

Indoor drain pipe I.D. 

mm 

Ф

30 

Indoor noise level 

dB(A) 

69 

Outdoor noise level 

dB(A) 

64 

Refrigerant  

Type \ 

R410A 

Recharged (After installation) 

9,500×2 

Control 

Thermostatic expansion valve 

Maximum refrigeration pipe pressure   

MPa 

4.4 

Refrigerant 

pipe 

Max. pipe length   

60 

Max. difference in level (O.U. up) 

20 

Max. difference in level (O.U. 

down) 

m 5 

Connection 

wire 

Indoor power wire 

mm

2

 

3×10.0mm

2

A,B,C

+2×6.0mm

2

N,GND

 

Outdoor power wire 

mm

2

 (4×1.0mm

2

)+ (4×1.0mm

2

Signal wire 

mm

2

 (4×1.0mm

2

)+ (4×1.0mm

2

Filter \ 

G4 

Indoor unit 

Net dimension (W×H×D) 

mm 

1,790×1,971×870 

Net weight 

kg 

665 

Outdoor unit 

(Single) 

Net dimension (W×H×D) 

mm 

1,470×988×690(No include supporting bar) 

Net weight 

kg 

105 

 

Notes: 

1.  The nominal cooling capacity is based on the following conditions. Indoor temperature: 24°CDB, 17°CWB; 

Outdoor temperature: 35°CDB, pipe length is 10 meters. 

2.  The noise is measured in the semi suppression lab. 
3.  Specifications are subject to change without prior notice for product improvement. 

 

 

 

 

 

 

 

 

 

All manuals and user guides at all-guides.com

Summary of Contents for MA0331

Page 1: ...Midea Precision Air Conditioner Technical Manual Down delivery series Midea reserves the right to discontinue or change specification or designs at any time without notices and without incurring oblig...

Page 2: ...SION UNIT MM 32 2 5 SERVICE SPACE 36 2 6 WIRING DIAGRAM 37 3 INSTALLATION 40 3 1 STORAGE ENVIRONMENT 42 3 2 INDOOR INSTALLATION 42 3 3 INSTALLING OUTDOOR UNITS 45 3 4 CONNECTING REFRIGERANT PIPE 46 3...

Page 3: ...UP CONTROL NETWORK SETTING 72 6 2 THE ETHERNET COMMUNICATION CARD INTRODUCTION 78 7 MAINTENANCE 81 7 1 ELECTRICAL MAINTENANCE 81 7 2 CONTROL MAINTENANCE 81 7 3 FILTER SCREEN MAINTENANCE 82 7 4 INDOOR...

Page 4: ...0V 3Ph 50Hz 40kW Indoor MAD040T2N1S1 1 790 1 971 870 2 380V 3Ph 50Hz Outdoor MA0331 1 470 988 870 380V 3Ph 50Hz 45kW Indoor MAD045T1N1S1 1 790 1 971 870 1 380V 3Ph 50Hz Outdoor MA0752 1 980 1 290 870...

Page 5: ...xtern Indoor Indoor Indoor on AC Technic nal appear r unit 20kW r unit 35kW r unit 70kW cal Manual rance 25kW 30k 40kW 45k 80kW 90k kW kW 50kW 6 kW 60kW M MCAC PDSM M 2013 01 All manuals and user guid...

Page 6: ...ome Indoor un M 2013 04 or unit Sing or unit Dou nclature nit gle fan moto uble fan mo or tors Midea a Precision AC Technical Ma anual Down Delivery Series 5 5 All manuals and user guides at all guide...

Page 7: ...ien technology o solution of h ocessor cont midity senso ormance evaporator area by elec ated casing nt compresso of immersed umidity trol technolo r frequency e r with hydro ctric valve to g reduces...

Page 8: ...yed i n be stored r password ction and joi nications an part and R ts Midea re protection n the screen maintenanc in in functio nd control RS485 card a Precision AC n discharge n of the cont ce passwo...

Page 9: ...Midea Precisi 8 2 2 Refrig Single on AC Technic gerant circ refrigerant cal Manual cuit t circuit type M MCAC PDSM M 2013 01 All manuals and user guides at all guides com...

Page 10: ...R41 rator Heat r Fan Centri or Fan Axia circuits type 0A scroll co exchanger ifugal fan al fan e ompressor Copper tu Midea ube and alum a Precision AC minum fin ty Technical Ma pe heat exc anual Down...

Page 11: ...heater Capacity W 6 000 Humidification Capacity kg h 5 Compressor Model ZP83KCE TFD 522 Type Scroll Qty 1 Brand Copeland Capacity W 20 000 Input W 6 400 Rated current RLA A 13 6 Locked rotor Amp LRA A...

Page 12: ...n pipe pressure MPa 4 4 Refrigerant pipe Max pipe length m 60 Max difference in level O U up m 20 Max difference in level O U down m 5 Connection wire Indoor power wire mm 2 3 10 0mm 2 A B C 2 6 0mm 2...

Page 13: ...000 Humidification Capacity kg h 5 Compressor Model ZP103KCE TFD 522 Type Scroll Qty 1 Brand Copeland Capacity W 25 200 Input W 7 800 Rated current RLA A 18 6 Locked rotor Amp LRA A 111 Thermal protec...

Page 14: ...4 4 Refrigerant pipe Max pipe length m 60 Max difference in level O U up m 20 Max difference in level O U down m 5 Connection wire Indoor power wire mm2 3 10 0mm 2 A B C 2 6 0mm 2 N GND Outdoor power...

Page 15: ...Humidification Capacity kg h 5 Compressor Model ZP120KCE TFD 522 Type Scroll Qty 1 Brand Copeland Capacity W 29 200 Input W 9 200 Rated current RLA A 20 Locked rotor Amp LRA A 118 Thermal protector In...

Page 16: ...ipe Max pipe length m 60 Max difference in level O U up m 20 Max difference in level O U down m 5 Connection wire Indoor power wire mm2 3 10 0mm 2 A B C 2 6 0mm 2 N GND Outdoor power wire mm2 4 1 0mm2...

Page 17: ...ity W 6 000 Humidification Capacity kg h 5 Compressor Model ZP137KCE TFD 522 Type Scroll Qty 1 Brand Copeland Capacity W 32 600 Input W 10 200 Rated current RLA A 20 7 Locked rotor Amp LRA A 118 Therm...

Page 18: ...essure MPa 4 4 Refrigerant pipe Max pipe length m 60 Max difference in level O U up m 20 Max difference in level O U down m 5 Connection wire Indoor power wire mm2 3 10 0mm 2 A B C 2 6 0mm 2 N GND Out...

Page 19: ...0 Humidification Capacity kg h 10 Compressor Model ZP83KCE TFD 522 Type Scroll Qty 2 Brand Copeland Capacity W 20 000 Input W 6 400 Rated current RLA A 13 6 Locked rotor Amp LRA A 101 Thermal protecto...

Page 20: ...ssure MPa 4 4 Refrigerant pipe Max pipe length m 60 Max difference in level O U up m 20 Max difference in level O U down m 5 Connection wire Indoor power wire mm2 3 10 0mm 2 A B C 2 6 0mm 2 N GND Outd...

Page 21: ...umidification Capacity kg h 10 Compressor Model ZP182KCE TFD 522 Type Scroll Qty 1 Brand Copeland Capacity W 44 000 Input W 13 500 Rated current RLA A 29 3 Locked rotor Amp LRA A 174 Thermal protector...

Page 22: ...pressure MPa 4 4 Refrigerant pipe Max pipe length m 60 Max difference in level O U up m 20 Max difference in level O U down m 5 Connection wire Indoor power wire mm2 3 10 0mm 2 A B C 2 6 0mm 2 N GND O...

Page 23: ...Humidification Capacity kg h 10 Compressor Model ZP103KCE TFD 522 Type Scroll Qty 2 Brand Copeland Capacity W 25 200 Input W 7 800 Rated current RLA A 18 6 Locked rotor Amp LRA A 111 Thermal protecto...

Page 24: ...ssure MPa 4 4 Refrigerant pipe Max pipe length m 60 Max difference in level O U up m 20 Max difference in level O U down m 5 Connection wire Indoor power wire mm2 3 10 0mm 2 A B C 2 6 0mm 2 N GND Outd...

Page 25: ...00 Humidification Capacity kg h 10 Compressor Model ZP120KCE TFD 522 Type Scroll Qty 2 Brand Copeland Capacity W 29 200 Input W 9 200 Rated current RLA A 20 Locked rotor Amp LRA A 118 Thermal protecto...

Page 26: ...Refrigerant pipe Max pipe length m 60 Max difference in level O U up m 20 Max difference in level O U down m 5 Connection wire Indoor power wire mm2 3 10 0mm 2 A B C 2 6 0mm 2 N GND Outdoor power wir...

Page 27: ...Humidification Capacity kg h 10 Compressor Model ZP137KCE TFD 522 Type Scroll Qty 2 Brand Copeland Capacity W 32 600 Input W 10 200 Rated current RLA A 20 7 Locked rotor Amp LRA A 118 Thermal protect...

Page 28: ...essure MPa 4 4 Refrigerant pipe Max pipe length m 60 Max difference in level O U up m 20 Max difference in level O U down m 5 Connection wire Indoor power wire mm2 3 10 0mm 2 A B C 2 6 0mm 2 N GND Out...

Page 29: ...00 Humidification Capacity kg h 10 Compressor Model ZP154KCE TFD 522 Type Scroll Qty 2 Brand Copeland Capacity W 37 300 Input W 11 600 Rated current RLA A 25 Locked rotor Amp LRA A 140 Thermal protect...

Page 30: ...essure MPa 4 4 Refrigerant pipe Max pipe length m 60 Max difference in level O U up m 20 Max difference in level O U down m 5 Connection wire Indoor power wire mm2 3 10 0mm 2 A B C 2 6 0mm 2 N GND Out...

Page 31: ...tion Capacity kg h 10 Compressor Model ZP182KCE TFD 522 Type Scroll Qty 2 Brand Copeland Capacity W 44 000 Input W 13 500 Rated current RLA A 29 3 Locked rotor Amp LRA A 174 Thermal protector Internal...

Page 32: ...essure MPa 4 4 Refrigerant pipe Max pipe length m 60 Max difference in level O U up m 20 Max difference in level O U down m 5 Connection wire Indoor power wire mm2 3 10 0mm 2 A B C 2 6 0mm 2 N GND Out...

Page 33: ...Midea Precisi 32 2 4 Dimen Indoor on AC Technic nsion Uni r unit MAD0 cal Manual t mm 020T1N1S1 MAD025T T1N1S1 MA AD030T1N1S M S1 MCAC PDSM M 2013 01 All manuals and user guides at all guides com...

Page 34: ...MCAC PDSM Indoor M 2013 04 r unit MAD0 035T1N1S1 Midea View of op a Precision AC pened door Technical Ma r anual Down Delivery Series 33 3 All manuals and user guides at all guides com...

Page 35: ...Indoor on AC Technic r unit MAD0 r unit MAD0 cal Manual 040T2N1S1 070T2N1S1 MAD045T MAD080T T1N1S1 MA T2N1S1 MA AD050T2N1S AD090T2N1S M S1 MAD060 S1 MCAC PDSM 0T2N1S1 M 2013 01 All manuals and user g...

Page 36: ...9 Mode MA033 MA043 MA054 MA060 MA075 MA098 431 MA054 982 el L 31 147 31 41 166 01 52 198 82 248 Midea 41 MA0601 L 70 9 60 1 80 80 a Precision AC H 988 290 Technical Ma W 690 anual Down Delivery Series...

Page 37: ...or Outdoo Outdoo on AC Technic ce space r unit Unit or unit with or unit with cal Manual mm h horizontal h vertical ins installation stallation U n Unit mm Unit mm M MCAC PDSM M 2013 01 All manuals an...

Page 38: ...M 3 2 Midea Precision AC 37 2 6 Wiring diag E box view o Technical Manual D gram of indoor unit Down Delivery Serie es MCA AC RTSM 2013 04 All manuals and user guides at all guides com...

Page 39: ...ith dual system MAD040T2N1S1 M tem Controlling MAD025T1N1S1 MA m Controlling c MAD050T2N1S1 MA g connection am AD030T1N1S1 an connection amp AD060T2N1S1 MA mplification figur d MAD035T1N1S plification...

Page 40: ...recisi 39 Outdoo Outdoo on AC Technic or unit MA or unit MA cal Manual Do A0331 MA04 A0752 MA09 own Delivery S 431 MA054 982 Series 41 MA0601 MCAC RT TSM 2013 04 All manuals and user guides at all gui...

Page 41: ...the ground nfirm whethe her the build ventilation p ctly follow th diagram ufacturer ne by technic n and mainten h of the pipe al componen he ground of of the outdo er the install dings need to pipe...

Page 42: ...i ure that the when the ind Midea ompressor i gerant back top elbow p door unit is h a Precision AC nstall revers kflow when t pipe of the re higher than Technical Ma se bend on t the units sto everse...

Page 43: ...nit in the nar en leads to a R No condensa C 54 C Out ransportation ed 6 months rding to the se was fixed nt control sy oof and heat ermal insulat ll must use p isture proof ncrease the y to minimize...

Page 44: ...position and e at the selec at and nuts t nit should no es and fixed n basing siz basing size Midea n place or at e huddled to upper part ze of the ind p of the insta d according cted position to fix...

Page 45: ...00 strong to su nd damage d e key places duction mat hape fixed m m e Unit mm m 5 Rubber rubber o 2 Install a This is o needs o upport the ind during trans s when the u terials before metal plates m r...

Page 46: ...please refers hods of insta door unit th pporting bar sories packa Midea t is damage unit intall th will block the ontal intall th dential area uilding pay s to the insta allation hor Verti ere are f...

Page 47: ...20 expan 6 20 expan ipe welding the ditioner syst the copper p ing measure ct with the w from the cop ality silver fib H1 764 1066 nsion bolt fo nsion bolt fo pipelines a tem which c pipes When ement...

Page 48: ...ng Midea nto the pipe size n height of u d add refrige ssor oil retu gn and cons r than 30m o berical show omponents b ition gher than ind wer than ind 5 meters of ollowing tab he installer w Equiva B...

Page 49: ...22mm Liquid pipe 13mm 13mm 13mm 13mm 13mm 16mm MAD045T1N1S1 Gas pipe 22mm 22mm 25mm 25mm 28mm 28mm Liquid pipe 16mm 16mm 16mm 16mm 19mm 19mm MAD050T2N1S1 Gas pipe 22mm 22mm 22mm 22mm 25mm 25mm Liquid...

Page 50: ...h is m rmal operatio Midea its lifespan T Be sure to ection as the ingle syste al system t een the indo m the outdo no problem p for 2 hours be green geration sys uitable amou r unit and ou more than...

Page 51: ...o diameter sho ld be conn ance is high tor should be terminal 01 here If the p he water frigerant amo efrigerant am Refrigeran refrigerant o re it needs 6 humidifier a of the tube ould be mini ected...

Page 52: ...C connected ssure range on the place et water coll ccordance w necting acce er pipe are o Midea th an inlet w for mainten let to the hu y PH SR 20 C TH CR R180 with outer w e of main p e pressure m le...

Page 53: ...ents c circuit use en closed ting holes to nd wiring fro wn the plate o the actual e power wi he electric c it power wiri and the gro ules s 380V AC e the voltme o passby the m the base of side pan ne...

Page 54: ...rolling con to outdoor u nnection amp Sing Dua nit wiring dia Midea plification fig gle system al system t agram as fo a Precision AC gure type type ollowing pict Technical Ma ture anual Down Delivery...

Page 55: ...shi er t the cables essor etc fo elding wire f with high te or protect th Single sys Dual syste for the outdo emperature o he insulation stem type m type oor parts of objects Suc layer M the connect c...

Page 56: ...an ht up means LCD manu any display obe reading e maintenan ng status pr ddress of cu put put output in ol plate Midea functions g or modifyi d silicone ru ans that unit ns one or m s that device ual...

Page 57: ...the alarm upper left c rsor moves upper left co es to a certa or from the u m and make anical part a K0 Time nd activate ti gram S1 e P0 User state can p m sound and corner click to a certain orner c...

Page 58: ...th re there are eeds to man o increase th woltage is i oor unit has ntrolling wire rolling conne are connec nd it can not ble and the quences of t needs to ma A B C of the n rovides the f omponents d...

Page 59: ...n to go bac djust the set r confirmatio he cursor po al compone on methods main interfac k message c et button to s r and use the ation ck to M0 pag tting paramt on sition and u nts and the ce and it...

Page 60: ...fication tank change from Water inletting to be Evaporating Press Manual drainage switch to drain off the water The first grade heater detection Operate two electrical heater switchs press Set to set...

Page 61: ...ine make sure the pipeline and the compressor cover have no condensed water and eliminate the potential liquid slugging danger Under the status of 24 C 50 RH air return and 29 30bar condensing pressur...

Page 62: ...fan main contro tandard use ndoor fan ompressor 1 ompressor 2 heater 1 heater 2 ehumidificat larm output umidifier umidifier wa umidifier wa ndoor fan reg Outdoor fan r Outdoor fan r Midea and cont Na...

Page 63: ...umidifier wa parkles alar ilter screen b Water leakag o 220V sign o 220V sign ndoor humid ir dischargin ir dischargin Outdoor temp ndoor tempe ir outlet tem lectric condu umidification S485 Conca r co...

Page 64: ...on Add the fun Midea ng to system m he previous m e alarm when t the menu to amend the d uick monitoring ata amending mend the funct ction code or a Precision AC Func monitoring sta menu the inverter...

Page 65: ...operation st he function cod the operating d the inverter to ad control sta ction code or e inverter unde e inverter unde g to the functio uter error inpu perating or jog down to stop top status nver...

Page 66: ...rect er pages for t point se enter the us omponent tly enter wit query Conte Midea etting func ser without ts operatin thout passw ents can be a Precision AC ction password ng status word Enter t chec...

Page 67: ...Midea Precisi 66 Note Interface on AC Technic es of Ig Ih Ii a cal Manual and Ij display y the humidif fier operating g status M MCAC PDSM M 2013 01 All manuals and user guides at all guides com...

Page 68: ...button in m is 0002 button to ent own to adju paramete menu it need ter the temp ust the param Midea ers d password t perature and meters settin a Precision AC to enter d humidity s ng Technical Ma s...

Page 69: ...to set temp Pb to Pj for a anagemen e button and tware versio e of hardwa tory alarm re gh interface o A6 erature settin et the deviati al functions a erature and h alarm selectio nt d enter the f on...

Page 70: ...intenance ment on and en e for mainten ton the disp ssword and password ter to the f Midea ance passwo play screen d then do th following in a Precision AC ord will pop up he calibratio terface and Te...

Page 71: ...K3 K4 t time zone fo Ka to change and type in ative functio elected Yes t some period to carry out t or controlling e the clock p clock mana ons of time z then can do s of a day a timer on and g inte...

Page 72: ...toge munication a ne controller ic paramter ach controlle 2 devicesw evice has th manual ope ol the units w he main unit ol of the shar ual operator e Three ma usly and the f this contro ontrollers b...

Page 73: ...s n to move the o be 00 n to confirm t etting ure an exam ess of the de wait the contr s to enter th e cursor to t the manual mple of how evice 2 to be roller finish o e configurat the 32 field operat...

Page 74: ...the conne at the same t op pressing matically shi d press ente ess of the de ottons at the splay as follo r to the 00 fi nual operato Midea ce 2 ections betw time and po ift to the follo er for confir...

Page 75: ...reen dis guring page to select the ller Use ent lowing address is 02 nual operator ller 02 is spec operator 2 ad oller 02 is sha ator 3 address ess 02 it is 2 ove the curs ontroller and same time owin...

Page 76: ...e ttons togethe nd type in pa the factory p ace of config Down butto by Down bu Midea n finish grou dresses of d the manual o splay ess No 32 w er to enter th assword by U password det guration ma on...

Page 77: ...ire cond rrent rotatio ut one rotati e as running s hours 000 t set the rota me zones ca two rotation nterface will erence betwe te standby a erence betwe lose standby uration man t then press are sev...

Page 78: ...twork 75mm2 is us onnect Rx T ers etwork work funcito ngle withou manual opera ccessively o Down Up an tatus of con No 32 pres U 01 U 02 U n the networ he operated tus And the o standby sta tation typ...

Page 79: ...hernet com work connec ctly connect heTCP IP co as following t communica card is insta ower Remov er power and perator addr eir correspo Gm interfac introduct mmuniction ctor and als ted with the ommu...

Page 80: ...g plu rts located o consequentl g the conne over supplie h the openin e MAC addr t network u own in follow w the data th munication c tioners and a Precision AC ug in connec on the case y it is recom...

Page 81: ...rd placemen ctured plastic rd into the c ic supports o the screwd er the RS485 nt cover with c the hole w correspondin on the pCO river making network is h a screwdriv which corres ng connecto case g...

Page 82: ...ntactor Tighten each electrical connecting terminal Check whether the plug in quick connectors whether contact well if there is any loose condition it should be replace the terminal 7 2 Control mainte...

Page 83: ...immedia hich have ex e indoor un necessary re uring instrum ature and h ect the humid the wind pow continually d need to adj contains a pa other cond away from th shall not dire he filter scr screen...

Page 84: ...f they are loosened they should be promptly tightened Fan bearing and impeller It should be regularly check whether the fan and fan spindle are installed firmly or not Turn the fan impeller to make su...

Page 85: ...p place it supply and e impurities ly tank whet clean or not s whether i mponent pa Nam Conductivi pipe of hum d valve 24V nage connec ng belt pipe of wate ector Conne ainage bend enoid valve so first...

Page 86: ...uppl op of the hum m the top of humidificatio of above ste k and use c e of humidific rtically take re body into les carefully cation tank c ating compo ment The in mperature sw ether the tem of the r...

Page 87: ...the needle valve of suction pipe 4 The sum total of above two pressure plus one local standard atmospheric pressure value then find out the corresponding saturated temperature of the saturation pressu...

Page 88: ...there is any error it also should be replaced Before the replacement clean the system is necessary by right method When changing the compressor the skin must be avoided to directly contact with the r...

Page 89: ...is broken off Manual reset check the average current value Contactor cannot contact together Check whether has 24V AC voltage between 28 and 03 Wire numbers If it has then the contactor has error cha...

Page 90: ...Check items or handling methods Compressor cannot run Power off Off the unit Check the main power switch fuse and connecting wires Power overload and the air switch broke off Manual reset check the c...

Page 91: ...or handling methods Low air suction pressure or return liquid Lack of refrigerant in system Check the leakage and maintain add refrigerant Air filter too dirty Change the air filter Drier filter is b...

Page 92: ...or measurement the range is AC500V If there is not equivalent voltage or no voltage then the inverter had been damaged Notes Between U V and W are high frequency impulse Code Type Error reason Solutio...

Page 93: ...hase error Current of 3 phase output side is asymmetric Check the output connecting wire and motor insulation E010 Out device error Out error signal input terminal activates Check the outer error reas...

Page 94: ...n frame sensor panel compon y nit Name manual of out components components oor unit for water nent tdoor unit Quantity 1 1 1 1 Quantity 1 4 24 Midea Shape Shape a Precision AC e Place e For ho For ho...

Page 95: ...e unit will alarm Operating hour threshold reached for compressor 1 Only remind need to cancel alarm Operating hour threshold reached for mail fan Only remind need to cancel alarm Room temperature pro...

Page 96: ...dress except address 1 0 is disconnected with controller of address 1 and it keeps 60s unit alarms Built in humidifier high conductivity alarm Switch off humidifier Conductivity of water inside humidi...