DM16-01.01.11-01en
Service
manual
Multi DC inverter R410A. Outdoor unit
9
Outdoor Model
M5OE-42HFN1-Q
Indoor unit combination
Single
Double
Three
FOUR
Five
Power supply
V-ph-Hz
220-240V- 50Hz, 1Ph
Cooling
Capacity
Btu/h
7000-18000 14000-28000 21000-36000 28000-40000 42000
Input
W
680-1800
1400-2780
2100-3450
2700-3700
3822
Rated current
A
3.0-8.0
6.2-11.8
9.0-15.0
11.6-16.0
16,6
EER
W/W
/
/
/
/
3,22
Heating
Capacity
Btu/h
7000-18000 14000-28000 21000-36000 28000-40000 42000
Input
W
680-1800
1400-2680
1995-3330
2580-3570
3372
Rated current
A
3.0-8.0
6.2-11.3
8.5-14.5
11.1-15.8
14,7
COP
W/W
/
/
/
/
3,65
Max. input consumption
W
4700
Max. input current
A
22
Compressor
Model
ATF310D43UMT
Type
ROTARY
Brand
GMCC
Capacity
Btu/h
32380
Input
W
2600
Rated current(RLA)
A
5,1
Locked rotor Amp(LRA)
A
-----
Thermal protector position
INTERNAL
Capacitor
μ
F -----
Refrigerant oil
ml
PQE(VG74)/1000
Outdoor fan
motor
New Model
ZKFN-120-8-2
Model
WZDK120-38G-W
Qty
1
Output W
120(Output)
Capacitor
μ
F -----
Speed(Hi/Med/Lo) r/min
900
Outdoor coil
Number of rows
2,6
Tube pitch(a)* row pitch(b)
mm
25.4x22
Fin spacing
mm
1.3
Fin type
Hydrophilic aluminium
Tube outside dia.and type
mm
Φ
9.52,innergroove tube
Coil length * height * width
mm
978580x762x22
Number of circuits
4
Outdoor air flow
m3/h
5500
Outdoor sound pressure level
dB(A)
62
Throttle type
CaEXV
Outdoor unit
Dimension(WxDxH) mm
946x410x810
Packing(WxDxH) mm
1090x500x865
Net/Gross weight
kg
76/81
Refrigerant
Type
R410A
GWP
2088
Charged quantity
Kg
3.6
Design pressure
MPa
4.2/1.5
Refrigerant
piping
Liquid side/ Gas side
mm(inch)
5 x
Φ
6.35/4x
Φ
9.52+1x
Φ
12.7(5x1/4"/4x3/8"+1x1/2")
Max. length for all rooms
m
75
Max. length for one indoor unit
m
30
Max. height difference
between indoor and
outdoor unit
OU higher
than IU
m 10
OU lower
than IU
m 15
Max. height difference between indoor
units
m 10
Ambient
temperature
Cooling
℃
-15-50
Heating
℃
-15-24
1.The above design and specifications are subject to change without prior notice for product improvement.
2.The values given in the table for the noise level reflect the levels in hemi-anechoic rooms.