Flooded type water cooled screw chiller (PCB Control)
MCAC-CTSM-2012-11
38
Current Data Display
Input
Click on “
” to enter “Input Page”
Input Status
“ON” as displayed indicates the input point is closed; “OFF” as displayed indicates the input point is
open.
Note:
①
“Remote Start/Stop” is available only under REMOTE mode. According to inching output from use’s
remote order, “Remote Start” or “Remote Stop” switch to ON and then revert to OFF rapidly.
②
“Chilled/Cooling Water Switch”: indicating that current water flow status of chilled water system.
“OFF” displayed in no water flow state, otherwise “ON”.
③
“Contactor Protection”: indicating that when the compressor start to run, the contactor act
normally, “OFF” switch to “ON”.
④
All of protection switches are “ON” in normal except “Comp. Overload Prot. Switch”. “Comp.
Overload Prot. Switch” is “ON” in failure status and “OFF” in normal.
Output Status
Click on “
” to enter “Output Page”,