M thermal Split
Pa
rt 2
-
Co
m
po
ne
nt
La
yo
ut
an
d R
efr
ige
ra
nt
Cir
cu
its
2 Piping Diagrams
2.1 Outdoor Unit Piping
Figure 2-2.1: Outdoor unit piping diagram
Legend
1
Compressor
7
Electronic expansion valve
2.1
Discharge pipe temperature sensor
8
Stop valve (liquid side)
2.2
Outdoor ambient temperature sensor
9
Stop valve (gas side)
2.3
Air side heat exchanger refrigerant outlet temperature sensor
10
Pressure sensor
2.4
Suction pipe temperature sensor
11
Separator
3
4-way valve
12.1
Low pressure switch
4
Air side heat exchanger
12.2
High pressure switch
5
Distributor
13
Capillary
6
Filter
14
Solenoid valve
Key components:
1.
Electronic expansion valve (EXV):
Controls refrigerant flow and reduces refrigerant pressure.
2.
Four-way valve:
Controls refrigerant flow direction. Closed in cooling mode and open in heating mode. When closed, the air side heat
exchanger functions as a condenser and water side heat exchanger functions as an evaporator; when open, the air
side heat exchanger functions as an evaporator and water side heat exchanger function as a condenser.
3.
High and low pressure switches:
Regulate refrigerant system pressure. When refrigerant system pressure rises above the upper limit or falls below the
lower limit, the high or low pressure switches turn off, stopping the compressor.
4.
Separator:
Separates liquid refrigerant from gas refrigerant to protect compressor from liquid hammering.
Air side heat exchanger
1
3
11
4
7
14
6
2.2
2.3
8
9
12.2
12.1
10
13
2.4
5
6
202004 13
Midea CAC Confidential
Summary of Contents for HB-A100/CGN8-B
Page 1: ...M Thermal A Series Split Commercial Air Conditioners R32 Service Manual Midea CAC Confidential...
Page 3: ...M thermal Split 2 202004 Midea M thermal Split Service Manual Midea CAC Confidential...
Page 7: ...M thermal Split 6 202004 Midea M thermal Split Service Manual Midea CAC Confidential...
Page 17: ...M thermal Split Midea M thermal Split Service Manual 16 202004 Midea CAC Confidential...